Product Model

ATV650D30N4EU

In Stock
Last updated: 2025/4/20
schneider ATV650D30N4EU

Selling Points

  • 1Up to 30% energy saving with the innovative "Stop and Go" feature.
  • 2Rated for 30 kW, 40 HP, and compatible with 380 to 480 V AC.
  • 3IP55 enclosure ensures protection against dust and water.
  • 4Supports Modbus TCP, Ethernet, and Modbus serial for seamless integration.
  • 5Suitable for material handling and hoisting applications with heavy-duty capabilities.
Product Details
ATV650D30N4EU
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Altivar Process ATV600
Product or Component Type
Variable speed drive
Product Specific Application
Process and utilities
Device short name
ATV650
Variant
With disconnect switch
Product destination
Asynchronous motors<br />Synchronous motors
EMC filter
Integrated 164.04 ft (50 m) IEC 61800-3 category C2<br />Integrated 492.1 ft (150 m) IEC 61800-3 category C3
IP degree of protection
IP55IEC 60529<br />IP55IEC 61800-5-1
[Us] rated supply voltage
380...480 V - 15...10 %
Degree of protection
UL type 12 UL 508C
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
22 kW heavy duty)<br />30 kW normal duty)
Maximum Horse Power Rating
30 hp heavy duty<br />40 hp normal duty
Line current
45.9 A 480 V normal duty)<br />40.5 A 380 V heavy duty)<br />35.8 A 480 V heavy duty)<br />53.3 A 380 V normal duty)
Prospective line Isc
50 kA
Apparent power
29.8 kVA 480 V heavy duty)<br />38.2 kVA 480 V normal duty)
Continuous output current
59 A 4 kHz normal duty<br />46.3 A 4 kHz heavy duty
Asynchronous motor control profile
Constant torque standard<br />Optimized torque mode<br />Optimized torque mode
Synchronous motor control profile
Synchronous reluctance motor<br />Permanent magnet motor
Speed drive output frequency
0.1…500 Hz
Nominal switching frequency
4 kHz
Switching frequency
4...12 kHz with derating factor<br />2...12 kHz adjustable
Safety function
STO (safe torque off) SIL 3
Discrete input logic
Positive logic (source) DI1...DI8), < 5 V, > 11 V<br />Negative logic (sink) DI1...DI8), > 16 V, < 10 V
communication port protocol
Ethernet<br />Modbus TCP<br />Modbus TCP
Option card
Slot A communication module, PROFINET<br />Slot A communication module, DeviceNet<br />Slot A communication module, Modbus TCP/EtherNet/IP<br />Slot A communication module, CANopen daisy chain RJ45<br />Slot A communication module, CANopen SUB-D 9<br />Slot A communication module, CANopen screw terminals<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module<br />Slot A communication module, Ethernet IP/Modbus TCP/MD-Link<br /> communication module, BACnet MS/TP<br /> communication module, Ethernet Powerlink<br />Slot A communication module, Profibus DP V1
Mounting Mode
Wall mount
Maximum transient current
69.5 A 60 s normal duty)<br />67.7 A 60 s heavy duty)
Phase
3 phase
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA<br />Relay outputs R1A, R1B, R1C 30 V DC 3000 mA<br />Relay outputs R2A, R2C 250 V AC 5000 mA<br />Relay outputs R2A, R2C 30 V DC 5000 mA<br />Relay outputs R3A, R3C 250 V AC 5000 mA<br />Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.5 x In 60 s heavy duty)<br />1.1 x In 60 s normal duty)
Motor slip compensation
Not available in permanent magnet motor law<br />Automatic whatever the load<br />Adjustable<br />Not available in permanent magnet motor law
Acceleration and deceleration ramps
Linear adjustable separately from 0.01...9999 s
Physical interface
Ethernet<br />2-wire RS 485
Braking to standstill
By DC injection
Protection type
Safe torque off motor<br />Motor phase break motor<br />Thermal protection drive<br />Safe torque off drive<br />Overheating drive<br />Overcurrent between output phases and earth drive<br />Overload of output voltage drive<br />Short-circuit protection drive<br />Motor phase break drive<br />Overvoltages on the DC bus drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overspeed drive<br />Break on the control circuit drive<br />Thermal protection motor
Transmission Rate
10, 100 Mbits<br />4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency resolution
Analog input 0.012/50 Hz<br />Display unit 0.1 Hz
Transmission frame
RTU
Electrical connection
Motor screw terminal 25...50 mm²<br />Line side screw terminal 25...50 mm²<br />Control removable screw terminals 0.5...1.5 mm²
Connector type
RJ45 on the remote graphic terminal)Modbus serial<br />RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses
1…247 Modbus serial
Method of access
Slave Modbus TCP
Supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection<br />External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection
Local signalling
for embedded communication status 3 LEDs (dual colour)<br /> for communication module status 4 LEDs (dual colour)<br /> for presence of voltage 1 LED (red)<br /> for local diagnostic 3 LEDs
Width
11.4 in (290 mm)
Height
35.8 in (910 mm)
Depth
15.8 in (401 mm)
Net Weight
110.2 lb(US) (50 kg)
Analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits<br />AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits<br />AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Discrete input number
8
Discrete input type
DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V)
Input compatibility
DI5, DI6 discrete input level 1 PLC IEC 65A-68<br />STOA, STOB discrete input level 1 PLC IEC 61131-2<br />DI1...DI6 discrete input level 1 PLC IEC 61131-2
Analogue output number
2
Analogue output type
Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits<br />Software-configurable current AQ1, AQ2 0...20 mA 10 bits<br />Software-configurable current DQ-, DQ+ 30 V DC<br />Software-configurable current DQ-, DQ+ 100 mA
Sampling duration
5 ms +/- 1 ms DI5, DI6) - discrete input<br />5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input<br />10 ms +/- 1 ms AO1) - analog output<br />2 ms +/- 0.5 ms DI1...DI4) - discrete input
Accuracy
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output<br />+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Linearity error
AO1, AO2 +/- 0.2 % analog output<br />AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Relay output number
3
Relay output type
Configurable relay logic R2 sequence relay NO 100000 cycles<br />Configurable relay logic R3 sequence relay NO 100000 cycles<br />Configurable relay logic R1 fault relay NO/NC 100000 cycles
Refresh time
Relay output R1, R2, R3)5 ms +/- 0.5 ms)
Minimum switching current
Relay output R1, R2, R3 5 mA 24 V DC
Maximum switching current
Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC<br />Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC
Isolation
Between power and control terminals
Maximum output frequency
500 kHz
Maximum Input Current per Phase
53.3 A
Quantity per Set
1
enclosure mounting
Wall mounted
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
69.7 dB
Operating position
Vertical +/- 10 degree
Maximum THDI
<48 % from 80...100 % of load IEC 61000-3-12
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6<br />Electrostatic discharge immunity test level 3 IEC 61000-4-2
Pollution degree
3
Vibration resistance
1 gn 13…200 Hz)IEC 60068-2-6<br />1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Relative humidity
5…95 % without condensation IEC 60068-2-3
Ambient air temperature for operation
104…122 °F (40…50 °C) with derating factor)<br />5…104 °F (-15…40 °C) without derating)
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Operating altitude
1000...4800 m with current derating 1 % per 100 m<br /><= 3280.84 ft (1000 m) without derating
Product Certifications
UL<br />DNV-GL<br />TÜV<br />ATEX INERIS<br />CSA<br />ATEX zone 2/22<br />Bureau Veritas
marking
CE
Standards
IEC 61800-3 environment 1 category C2<br />EN/IEC 61800-3 environment 2 category C3<br />IEC 61800-5-1<br />IEC 61000-3-12<br />IEC 60721-3<br />IEC 61508<br />IEC 13849-1<br />IEC 61800-3
Overvoltage category
III
Regulation loop
Adjustable PID regulator

Specifications may be subject to change without notice