Product Model

BMXAMI0410

In Stock
Last updated: 2025/4/18
schneider BMXAMI0410

Selling Points

  • 1High-Level Isolation: Provides 300V DC isolation between channels and 1400V DC isolation between channels and ground.
  • 2Robust Performance: Designed for continuous process monitoring, measurement, and control with 16-bit resolution.
  • 3Versatile Inputs: Supports various input ranges including 0-20mA, 4-20mA, ±10V, ±5V, and 0-5V.
  • 4Compact Design: Occupies a single slot in the rack with IP20 protection.
  • 5Reliable Operation: Offers a minimum crosstalk attenuation of 80 dB and EMI/RFI noise rejection up to 90 dB.
Product Details
BMXAMI0410
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
Analog input module
Electrical connection
20 ways 1 connector
Isolation between channels
Isolated
Input level
High level
Analogue input number
4
Analogue input type
Current +/- 20 mA<br />Current 0...20 mA<br />Current 4...20 mA<br />Voltage +/- 10 V<br />Voltage +/- 5 V<br />Voltage 0...10 V<br />Voltage 0...5 V<br />Voltage 1...5 V
Analog/digital conversion
24 bits
Analogue input resolution
16 bits
Permitted overload on inputs
+/- 30 V +/- 10 V<br />+/- 30 V +/- 5 V<br />+/- 30 V 0...10 V<br />+/- 30 V 0...5 V<br />+/- 30 V 1...5 V<br />+/- 90 mA +/- 20 mA<br />+/- 90 mA 0...20 mA<br />+/- 90 mA 4...20 mA
Input impedance
10 MOhm in voltage mode<br />250 Ohm + 3.6...50 Ohm internal protective resistor in current mode
Precision of internal conversion resistor
0.1 % - 15 ppm/°C
Type of filter
First order digital filtering
Fast read cycle time
1 ms + 1 ms x number of channels used
Nominal read cycle time
5 ms for 4 channels
Measurement error
<= 0.1 % of full scale +/- 10 V 0...60 °C<br /><= 0.1 % of full scale +/- 5 V 0...60 °C<br /><= 0.1 % of full scale 0...10 V 0...60 °C<br /><= 0.1 % of full scale 0...5 V 0...60 °C<br /><= 0.1 % of full scale 1...5 V 0...60 °C<br /><= 0.3 % of full scale +/- 20 mA 0...60 °C<br /><= 0.3 % of full scale 0...20 mA 0...60 °C<br /><= 0.3 % of full scale 4...20 mA 0...60 °C<br />0.075 % of full scale +/- 10 V 25 °C<br />0.075 % of full scale +/- 5 V 25 °C<br />0.075 % of full scale 0...10 V 25 °C<br />0.075 % of full scale 0...5 V 25 °C<br />0.075 % of full scale 1...5 V 25 °C<br />0.15 % of full scale +/- 20 mA 25 °C<br />0.15 % of full scale 0...20 mA 25 °C<br />0.15 % of full scale 4...20 mA 25 °C
Temperature drift
15 ppm/°C +/- 10 V<br />15 ppm/°C +/- 5 V<br />15 ppm/°C 0...10 V<br />15 ppm/°C 0...5 V<br />15 ppm/°C 1...5 V<br />30 ppm/°C +/- 20 mA<br />30 ppm/°C 0...20 mA<br />30 ppm/°C 4...20 mA
Recalibration
Internal
Minimum crosstalk attenuation
80 dB
Common mode rejection
90 dB
Digital value format
- 32768 to + 32767 in maximum user scale<br />+/- 10000 by default
Isolation voltage
300 V DC between channels<br />1400 V DC between channels and ground<br />1400 V DC between channels and bus
Measurement resolution
0.35 mV +/- 10 V<br />0.35 mV +/- 5 V<br />0.35 mV 0...10 V<br />0.35 mV 0...5 V<br />0.35 mV 1...5 V<br />0.92 µA +/- 20 mA<br />0.92 µA 0...20 mA<br />0.92 µA 4...20 mA
Maximum conversion value
+/- 11.4 V +/- 10 V<br />+/- 11.4 V +/- 5 V<br />+/- 11.4 V 0...10 V<br />+/- 11.4 V 0...5 V<br />+/- 11.4 V 1...5 V<br />0...30 mA +/- 20 mA<br />0...30 mA 0...20 mA<br />0...30 mA 4...20 mA
MTBF reliability
1200000 H
Operating altitude
0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor
Status LED
1 LED (Green) RUN<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) ERR<br />1 LED (Red) I/O
Net Weight
0.315 lb(US) (0.143 kg)
Power consumption in W
0.82 W 24 V DC typical<br />1.30 W 24 V DC maximum<br />0.32 W 3.3 V DC typical<br />0.48 W 3.3 V DC maximum
Current consumption
150 mA 3.3 V DC<br />45 mA 24 V DC
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Relative humidity
5…95 % 131 °F (55 °C) without condensation
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility
Product Certifications
CE<br />RCM<br />CSA<br />EAC<br />Merchant Navy<br />UL
Standards
EN/IEC 61010-2-201<br />EN/IEC 61131-2<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201

Specifications may be subject to change without notice