Product Model
BMXAMI0410H

Selling Points
- 1High Accuracy & Resolution: 16-bit resolution for precise analog input.
- 2Isolated Analog Inputs: Isolated channels ensure reliable data transmission.
- 3Severe Environment Ready: Designed for harsh environments with a temperature range of -25 to 70°C.
- 4Versatile Signal Range: Supports +/- 10 V, 0 to 20/4 to 20 mA signal types.
- 5Compact Design: Dimensions of 3.93 in H x 6.29 in D for easy integration.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon X80 | Product or Component Type | Analog input module |
Product Specific Application | For severe environments | Electrical connection | 20 ways 1 connector |
Isolation between channels | Isolated | Input level | High level |
Analogue input number | 4 | Analogue input type | Current +/- 20 mA<br />Current 0...20 mA<br />Current 4...20 mA<br />Voltage +/- 10 V<br />Voltage +/- 5 V<br />Voltage 0...10 V<br />Voltage 0...5 V<br />Voltage 1...5 V |
Analog/digital conversion | 24 bits | Analogue input resolution | 16 bits |
Permitted overload on inputs | +/- 30 V +/- 10 V<br />+/- 30 V +/- 5 V<br />+/- 30 V 0...10 V<br />+/- 30 V 0...5 V<br />+/- 30 V 1...5 V<br />+/- 90 mA +/- 20 mA<br />+/- 90 mA 0...20 mA<br />+/- 90 mA 4...20 mA | Input impedance | 10 MOhm in voltage mode<br />250 Ohm + 3.6...50 Ohm internal protective resistor in current mode |
Precision of internal conversion resistor | 0.1 % - 15 ppm/°C | Type of filter | First order digital filtering |
Fast read cycle time | 1 ms + 1 ms x number of channels used | Nominal read cycle time | 5 ms for 4 channels |
Measurement error | 0.075 % of full scale +/- 10 V 25 °C<br />0.075 % of full scale +/- 5 V 25 °C<br />0.075 % of full scale 0...10 V 25 °C<br />0.075 % of full scale 0...5 V 25 °C<br />0.075 % of full scale 1...5 V 25 °C<br />0.15 % of full scale +/- 20 mA 25 °C<br />0.15 % of full scale 0...20 mA 25 °C<br />0.15 % of full scale 4...20 mA 25 °C<br /><= 0.2 % of full scale +/- 10 V - 25...70 °C<br /><= 0.2 % of full scale +/- 5 V - 25...70 °C<br /><= 0.2 % of full scale 0...10 V - 25...70 °C<br /><= 0.2 % of full scale 0...5 V - 25...70 °C<br /><= 0.2 % of full scale 1...5 V - 25...70 °C<br /><= 0.55 % of full scale +/- 20 mA - 25...70 °C<br /><= 0.55 % of full scale 0...20 mA - 25...70 °C<br /><= 0.55 % of full scale 4...20 mA - 25...70 °C | Temperature drift | 15 ppm/°C +/- 10 V<br />15 ppm/°C +/- 5 V<br />15 ppm/°C 0...10 V<br />15 ppm/°C 0...5 V<br />15 ppm/°C 1...5 V<br />30 ppm/°C +/- 20 mA<br />30 ppm/°C 0...20 mA<br />30 ppm/°C 4...20 mA |
Recalibration | Internal | Minimum crosstalk attenuation | 80 dB |
Common mode rejection | 90 dB | Digital value format | - 32768 to + 32767 in maximum user scale<br />+/- 10000 by default |
Isolation voltage | 300 V DC between channels<br />1400 V DC between channels and ground<br />1400 V DC between channels and bus | Measurement resolution | 0.35 mV +/- 10 V<br />0.35 mV +/- 5 V<br />0.35 mV 0...10 V<br />0.35 mV 0...5 V<br />0.35 mV 1...5 V<br />0.92 µA +/- 20 mA<br />0.92 µA 0...20 mA<br />0.92 µA 4...20 mA |
Maximum conversion value | +/- 11.4 V +/- 10 V<br />+/- 11.4 V +/- 5 V<br />+/- 11.4 V 0...10 V<br />+/- 11.4 V 0...5 V<br />+/- 11.4 V 1...5 V<br />0...30 mA +/- 20 mA<br />0...30 mA 0...20 mA<br />0...30 mA 4...20 mA | MTBF reliability | 1200000 H |
Operating altitude | 0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor | Status LED | 1 LED (Green) RUN<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) ERR<br />1 LED (Red) I/O |
Net Weight | 0.315 lb(US) (0.143 kg) | Power consumption in W | 0.82 W 24 V DC typical<br />1.30 W 24 V DC maximum<br />0.32 W 3.3 V DC typical<br />0.48 W 3.3 V DC maximum |
Current consumption | 150 mA 3.3 V DC<br />45 mA 24 V DC | Vibration resistance | 3 gn |
Shock resistance | 30 gn | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Ambient Air Temperature for Operation | -13…158 °F (-25…70 °C) | Relative humidity | 5…95 % 131 °F (55 °C) without condensation |
IP Degree of Protection | IP20 | Directives | 2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility |
Product Certifications | CE<br />RCM<br />CSA<br />EAC<br />Merchant Navy<br />UL<br />ATEX<br />IEC-Ex | Standards | EN/IEC 61010-2-201<br />EN/IEC 61131-2<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201 |
Environmental characteristic | Gas resistant class Gx<br />Gas resistant class 3C4<br />Dust resistant class 3S4<br />Sand resistant class 3S4<br />Salt resistant level 2<br />Mold growth resistant class 3B2<br />Fungal spore resistant class 3B2<br />Hazardous location | Protective treatment | Conformal coating |
Specifications may be subject to change without notice