Product Model

BMXAMI0800

In Stock
Last updated: 2025/4/18
schneider BMXAMI0800

Selling Points

  • 1Precise Data Acquisition: The BMXAMI0800 module provides accurate analog input with 16-bit conversion and a resolution of 15 bits plus sign.
  • 2Versatile Input Types: Supports current and voltage inputs including 0–20 mA, 4–20 mA, ±10 V, and ±5 V for diverse industrial applications.
  • 3Fast Read Cycle Time: Ensures rapid data acquisition with a fast read cycle time of 1 ms per channel.
  • 4Robust Overload Protection: Offers ±30 mA overload protection for current inputs and ±30 V overload protection for voltage inputs.
  • 5Seamless Integration: Designed for seamless integration with Schneider Electric’s Modicon X80 automation systems.
Product Details
BMXAMI0800
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
Analog input module
Electrical connection
28 ways 1 connector
Isolation between channels
Non isolated
Input level
High level
Analogue input number
8
Analogue input type
Current +/- 20 mA<br />Current 0...20 mA<br />Current 4...20 mA<br />Voltage +/- 10 V<br />Voltage +/- 5 V<br />Voltage 0...10 V<br />Voltage 0...5 V<br />Voltage 1...5 V
Analog/digital conversion
16 bits
Analogue input resolution
15 bits + sign
Permitted overload on inputs
+/- 30 mA 0...20 mA<br />+/- 30 mA 4...20 mA<br />+/- 30 V +/- 10 V<br />+/- 30 V +/- 5 V<br />+/- 30 V 0...10 V<br />+/- 30 V 0...5 V<br />+/- 30 V 1...5 V<br />+/- 30 mA +/- 20 mA
Input impedance
10 MOhm in voltage mode<br />250 Ohm in current mode
Precision of internal conversion resistor
0.1 % - 15 ppm/°C
Type of filter
First order digital filtering
Fast read cycle time
1 ms + 1 ms x number of channels used
Nominal read cycle time
9 ms for 8 channels
Measurement error
<= 0.1 % of full scale +/- 10 V 0...60 °C<br /><= 0.1 % of full scale +/- 5 V 0...60 °C<br /><= 0.1 % of full scale 0...10 V 0...60 °C<br /><= 0.1 % of full scale 0...5 V 0...60 °C<br /><= 0.1 % of full scale 1...5 V 0...60 °C<br /><= 0.3 % of full scale +/- 20 mA 0...60 °C<br /><= 0.3 % of full scale 0...20 mA 0...60 °C<br /><= 0.3 % of full scale 4...20 mA 0...60 °C<br />0.15 % of full scale +/- 20 mA 25 °C<br />0.15 % of full scale 0...20 mA 25 °C<br />0.15 % of full scale 4...20 mA 25 °C<br />0.075 % of full scale +/- 10 V 25 °C<br />0.075 % of full scale 0...10 V 25 °C<br />0.075 % of full scale 0...5 V 25 °C<br />0.075 % of full scale 1...5 V 25 °C<br />0.075 % of full scale +/- 5 V 25 °C
Temperature drift
30 ppm/°C +/- 10 V<br />30 ppm/°C +/- 5 V<br />30 ppm/°C 0...10 V<br />30 ppm/°C 0...5 V<br />30 ppm/°C 1...5 V<br />50 ppm/°C +/- 20 mA<br />50 ppm/°C 0...20 mA<br />50 ppm/°C 4...20 mA
Recalibration
Factory calibrated
Minimum crosstalk attenuation
80 dB
Common mode rejection
100 dB
Digital value format
- 32768 to + 32767 in maximum user scale<br />+/- 10000 by default
Isolation voltage
1400 V DC between channels and ground<br />1400 V DC between channels and bus<br />50 V DC between channels
Measurement resolution
0.36 mV +/- 10 V<br />0.36 mV 0...10 V<br />0.36 mV 0...5 V<br />0.36 mV 1...5 V<br />0.36 mV +/- 5 V<br />1.4 µA +/- 20 mA<br />1.4 µA 0...20 mA<br />1.4 µA 4...20 mA
Maximum conversion value
+/- 11.4 V +/- 10 V<br />+/- 11.4 V 0...10 V<br />+/- 11.4 V 0...5 V<br />+/- 11.4 V 1...5 V<br />0...30 mA +/- 20 mA<br />0...30 mA 0...20 mA<br />0...30 mA 4...20 mA<br />0...30 mA +/- 5 V
MTBF reliability
1700000 H
Operating altitude
0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor
Status LED
1 LED (Green) RUN<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) ERR<br />1 LED (Red) I/O
Net Weight
0.364 lb(US) (0.165 kg)
Power consumption in W
0.90 W 24 V DC typical<br />1.10 W 24 V DC maximum<br />0.32 W 3.3 V DC typical<br />0.48 W 3.3 V DC maximum
Current consumption
150 mA 3.3 V DC<br />41 mA 24 V DC
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Relative humidity
5…95 % 131 °F (55 °C) without condensation
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility
Product Certifications
CE<br />RCM<br />CSA<br />EAC<br />Merchant Navy<br />UL
Standards
EN/IEC 61010-2-201<br />EN/IEC 61131-2<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201

Specifications may be subject to change without notice