Product Model

BMXDDM16025H

In Stock
Last updated: 2025/4/18
schneider BMXDDM16025H

Selling Points

  • 1High Reliability: Designed for severe environments with a MTBF of 940,000 hours.
  • 2Versatile Connectivity: Compatible with 2-wire/3-wire proximity sensors and IEC 60947-5-2 standards.
  • 3Efficient Operation: Typical current consumption of 79 mA and response time of 4 ms.
  • 4Durable Construction: Insulation resistance > 10 MOhm and mechanical durability of 20 million cycles.
  • 5Comprehensive Safety Features: Reverse polarity protection and external fuses for enhanced safety.
Product Details
BMXDDM16025H
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
Discrete I/O module
Product Specific Application
For severe environments
Discrete input number
8
input type
Current sink (logic positive)
Discrete input voltage
24 V DC positive
Discrete input current
3.5 mA
Discrete output number
8
Discrete output type
Relay
Discrete output voltage
24 V 19...30 V DC<br />24...240 V 19...264 V AC
Discrete output current
2000 mA
Input compatibility
With 2-wire/3-wire proximity sensors IEC 60947-5-2<br />With 2-wire/3-wire proximity sensors IEC 61131-2 type 3
Sensor power supply
19...30 V 140 °F (60 °C)<br />21.1...29.0 V 158 °F (70 °C)
Current state 1 guaranteed
>= 2 mA
Current state 0 guaranteed
<= 1.5 mA
input impedance
6800 Ohm
Insulation resistance
> 10 MOhm 500 V DC
Power dissipation in W
3.1 W
DC typical response time
4 ms
DC maximum response time
7 ms
Response time on output
<= 8 ms deactivation<br /><= 10 ms activation
Paralleling of inputs
No
Typical current consumption
79 mA 3.3 V DC
MTBF reliability
940000 H
Protection type
1 external fuse per group of input channel 0.5 A fast blow<br /> reverse polarity protection on input<br /> 1 external fuse per output channel or group of output channel fast blow
Voltage detection threshold
< 14 V DC sensor fault<br />> 18 V DC sensor OK
Minimum switching current
1 mA 5 V DC
Maximum switching voltage
125 V DC<br />264 V AC
Mechanical durability
20000000 cycles
Electrical durability
AC-14 100000 cycles 120 VA 240 V 158 °F (70 °C) 0.7)<br />AC-14 100000 cycles 150 VA 200 V 158 °F (70 °C) 0.7)<br />AC-14 100000 cycles 240 VA 240 V -13…140 °F (-25…60 °C) 0.7)<br />AC-14 100000 cycles 300 VA 200 V -13…140 °F (-25…60 °C) 0.7)<br />AC-15 100000 cycles 100 VA 200 V 158 °F (70 °C) 0.35)<br />AC-15 100000 cycles 120 VA 240 V -13…140 °F (-25…60 °C) 0.35)<br />AC-15 100000 cycles 200 VA 200 V -13…140 °F (-25…60 °C) 0.35)<br />AC-15 100000 cycles 60 VA 240 V 158 °F (70 °C) 0.35)<br />DC-13 100000 cycles 12 W 24 V 158 °F (70 °C)<br />DC-13 100000 cycles 24 W 24 V -13…140 °F (-25…60 °C)<br />AC-14 300000 cycles 36 VA 240 V 158 °F (70 °C) 0.7)<br />AC-14 300000 cycles 40 VA 200 V 158 °F (70 °C) 0.7)<br />AC-14 300000 cycles 72 VA 240 V -13…140 °F (-25…60 °C) 0.7)<br />AC-14 300000 cycles 80 VA 200 V -13…140 °F (-25…60 °C) 0.7)<br />AC-15 300000 cycles 18 VA 240 V 158 °F (70 °C) 0.35)<br />AC-15 300000 cycles 30 VA 200 V 158 °F (70 °C) 0.35)<br />AC-15 300000 cycles 36 VA 240 V -13…140 °F (-25…60 °C) 0.35)<br />AC-15 300000 cycles 60 VA 200 V -13…140 °F (-25…60 °C) 0.35)<br />DC-13 300000 cycles 3.6 W 24 V 158 °F (70 °C)<br />DC-13 300000 cycles 7.2 W 24 V -13…140 °F (-25…60 °C)
Switching frequency
1 Hz
Status LED
1 LED (Green) module operating (RUN)<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) module error (ERR)<br />1 LED (Red) module I/O
Net Weight
0.298 lb(US) (0.135 kg)
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility
Environmental characteristic
Gas resistant class Gx<br />Gas resistant class 3C4<br />Dust resistant class 3S4<br />Sand resistant class 3S4<br />Salt resistant level 2<br />Mold growth resistant class 3B2<br />Fungal spore resistant class 3B2
Dielectric strength
1500 V AC 50/60 Hz 1 minute, primary/secondary<br />2830 V AC 50/60 Hz 1 minute, output relay<br />500 V DC 1 minute, between group of I/O
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % 131 °F (55 °C) without condensation
Protective treatment
Conformal coating
Operating altitude
0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor

Specifications may be subject to change without notice