Product Model
BMXDRA0805

Selling Points
- 1Provides precise control with 8 normally open (NO) relay outputs.
- 2Operates on 24 to 240V AC or 12 to 24V DC, ensuring versatility in industrial setups.
- 3Ensures efficient operation with a power dissipation of 2.7W and insulation resistance >10 MOhm at 500V DC.
- 4Simplifies diagnostics with LED indicators for RUN, channel diagnostics, ERR, and I/O status.
- 5Designed with IP20 protection, resistance to corrosion and dust, and withstands dielectric strength tests of 2000V AC at 50/60 Hz for 1 minute.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon X80 | Product or Component Type | Discrete output module |
Discrete output number | 8 EN/IEC 61131-2 | Discrete output type | Relay |
Discrete output voltage | 24...240 V 19...264 V AC<br />12...24 V 10...34 V DC | [Ith] conventional free air thermal current | 3 A |
Insulation resistance | > 10 MOhm 500 V DC | Power dissipation in W | 2.7 W |
Response time on output | < 10 ms activation<br />< 8 ms deactivation | Typical current consumption | 79 mA 3.3 V DC |
MTBF reliability | 2119902 H | Output overload protection | Use 1 fast blow fuse per channel or group of channel |
Output overvoltage protection | Use discharge diode on each output DC<br />Use RC circuit on each output AC<br />Use ZNO surge limiter on each output AC | Output short-circuit protection | Use 1 fast blow fuse per channel or group of channel |
Minimum switching current | 10 mA 5 V DC | Electrical durability | AC-15 100000 cycles 220 VA 200...240 V 0.35)<br />AC-12 1000000 cycles 110 VA 110...120 V<br />AC-12 1000000 cycles 220 VA 200...240 V<br />AC-12 1000000 cycles 50 VA 48 V<br />AC-15 1000000 cycles 110 VA 200...240 V 0.35)<br />DC-12 1000000 cycles 24 W 24 V<br />DC-13 1000000 cycles 24 W 24 V<br />AC-15 10000000 cycles 10 VA 110...120 V 0.35)<br />AC-15 10000000 cycles 10 VA 200...240 V 0.35)<br />AC-15 150000 cycles 110 VA 110...120 V 0.35)<br />AC-15 1500000 cycles 50 VA 110...120 V 0.35)<br />AC-15 2000000 cycles 24 VA 48 V 0.35)<br />DC-13 2000000 cycles 10 W 24 V<br />DC-12 300000 cycles 40 W 24 V<br />AC-15 3000000 cycles 50 VA 200...240 V 0.35)<br />AC-12 500000 cycles 110 VA 48 V<br />AC-12 500000 cycles 220 VA 110...120 V<br />AC-15 5000000 cycles 10 VA 48 V 0.35)<br />AC-15 500000 cycles 24 VA 24 V 0.35)<br />AC-12 700000 cycles 50 VA 24 V |
Status LED | 1 LED (Green) module operating (RUN)<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) module error (ERR)<br />1 LED (Red) module I/O | Net Weight | 0.320 lb(US) (0.145 kg) |
IP Degree of Protection | IP20 | Directives | 2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility |
Environmental characteristic | Corrosion resistance<br />Dust resistant | Dielectric strength | 2000 V AC 50/60 Hz 1 min |
Vibration resistance | 3 gn | Shock resistance | 30 gn |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Relative humidity | 5…95 % 131 °F (55 °C) without condensation | Operating altitude | 0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor |
Specifications may be subject to change without notice