Product Model
BMXDRA0815H

Selling Points
- 1Robust Design for Severe Environments: Built to withstand temperatures from -40 to 85 degrees Fahrenheit.
- 2Versatile Voltage Ratings: Compatible with 24 to 240V AC and 24 to 125V DC.
- 38 NO Relay Outputs: Provides reliable and efficient control for various applications.
- 4High-Quality Reliability: Manufactured by Schneider Electric, known for its high-quality electrical components.
- 5Compliance with Regulations: Meets RoHS and REACH compliance standards for environmental safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon X80 | Product or Component Type | Relay discrete output module |
Product Specific Application | For severe environments | Discrete output number | 8 EN/IEC 61131-2 |
Discrete output logic | Positive | Discrete output voltage | 24...240 V 19...264 V AC<br />24...125 V 5...150 V DC |
Electrical connection | 20 ways terminal block | Network Frequency | 50/60 Hz |
Network frequency limits | 47…63 Hz | Sensor power supply | 5...150 V<br />19...264 V |
[Ith] conventional free air thermal current | 3 A | Insulation resistance | > 10 MOhm 500 V DC |
Power dissipation in W | 3.6 W | Response time on output | <= 10 ms activation<br /><= 13 ms deactivation |
Typical current consumption | 40 mA 3.3 V DC<br />101 mA 24 V DC | MTBF reliability | 3200000 H |
Protection type | External short-circuit protection<br />External overload protection<br />External overvoltage protection, inductive AC<br />External overvoltage protection, inductive DC | Output overload protection | Use 1 fast blow fuse per channel or group of channel |
Output overvoltage protection | Use discharge diode on each output DC<br />Use RC circuit on each output AC<br />Use ZNO surge limiter on each output AC | Output short-circuit protection | Use 1 fast blow fuse per channel or group of channel |
Minimum switching current | 1 mA 5 V DC | Electrical durability | AC-12 200000 cycles 48 VA 24 V -13…140 °F (-25…60 °C)<br />AC-12 200000 cycles 28.8 VA 24 V 158 °F (70 °C)<br />AC-12 300000 cycles 48 VA 48 V -13…140 °F (-25…60 °C)<br />AC-12 300000 cycles 28.8 VA 48 V 158 °F (70 °C)<br />AC-12 150000 cycles 96 VA 48 V -13…140 °F (-25…60 °C)<br />AC-12 150000 cycles 57.6 VA 48 V 158 °F (70 °C)<br />AC-12 300000 cycles 110 VA 100...120 V -13…140 °F (-25…60 °C)<br />AC-12 300000 cycles 66 VA 100...120 V 158 °F (70 °C)<br />AC-12 150000 cycles 220 VA 100...120 V -13…140 °F (-25…60 °C)<br />AC-12 150000 cycles 132 VA 100...120 V 158 °F (70 °C)<br />AC-12 300000 cycles 220 VA 200...250 V -13…140 °F (-25…60 °C)<br />AC-12 300000 cycles 132 VA 200...250 V 158 °F (70 °C)<br />AC-12 150000 cycles 500 VA 200...250 V -13…140 °F (-25…60 °C)<br />AC-12 150000 cycles 300 VA 200...250 V 158 °F (70 °C)<br />AC-15 700000 cycles 10 VA 24 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 700000 cycles 6 VA 24 V 158 °F (70 °C) 0.4)<br />AC-15 500000 cycles 24 VA 24 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 500000 cycles 14.4 VA 24 V 158 °F (70 °C) 0.4)<br />AC-15 200000 cycles 48 VA 24 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 200000 cycles 28.8 VA 24 V 158 °F (70 °C) 0.4)<br />AC-15 700000 cycles 10 VA 48 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 700000 cycles 6 VA 48 V 158 °F (70 °C) 0.4)<br />AC-15 500000 cycles 24 VA 48 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 500000 cycles 14.4 VA 48 V 158 °F (70 °C) 0.4)<br />AC-15 300000 cycles 48 VA 48 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 300000 cycles 28.8 VA 48 V 158 °F (70 °C) 0.4)<br />AC-15 100000 cycles 96 VA 48 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 100000 cycles 57.6 VA 48 V 158 °F (70 °C) 0.4)<br />AC-15 1000000 cycles 10 VA 100...120 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 1000000 cycles 6 VA 100...120 V 158 °F (70 °C) 0.4)<br />AC-15 300000 cycles 50 VA 100...120 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 300000 cycles 30 VA 100...120 V 158 °F (70 °C) 0.4)<br />AC-15 200000 cycles 110 VA 100...120 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 200000 cycles 66 VA 100...120 V 158 °F (70 °C) 0.4)<br />AC-15 70000 cycles 220 VA 100...120 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 70000 cycles 132 VA 100...120 V 158 °F (70 °C) 0.4)<br />AC-15 1000000 cycles 10 VA 200...250 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 1000000 cycles 6 VA 200...250 V 158 °F (70 °C) 0.4)<br />AC-15 500000 cycles 50 VA 200...250 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 500000 cycles 30 VA 200...250 V 158 °F (70 °C) 0.4)<br />AC-15 200000 cycles 110 VA 200...250 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 200000 cycles 66 VA 200...250 V 158 °F (70 °C) 0.4)<br />AC-15 150000 cycles 220 VA 200...250 V -13…140 °F (-25…60 °C) 0.4)<br />AC-15 150000 cycles 132 VA 200...250 V 158 °F (70 °C) 0.4)<br />DC-12 200000 cycles 24 W 24 V -13…140 °F (-25…60 °C)<br />DC-12 200000 cycles 14.4 W 24 V 158 °F (70 °C)<br />DC-12 150000 cycles 48 W 24 V -13…140 °F (-25…60 °C)<br />DC-12 150000 cycles 28.8 W 24 V 158 °F (70 °C)<br />DC-12 150000 cycles 40 W 48...60 V -13…140 °F (-25…60 °C)<br />DC-12 150000 cycles 24 W 48...60 V 158 °F (70 °C)<br />DC-12 100000 cycles 45 W 100...125 V -13…140 °F (-25…60 °C)<br />DC-12 60000 cycles 45 W 100...125 V 158 °F (70 °C)<br />DC-13 100000 cycles 10 W 24 V -13…140 °F (-25…60 °C)<br />DC-13 100000 cycles 6 W 24 V 158 °F (70 °C)<br />DC-13 60000 cycles 24 W 24 V -13…140 °F (-25…60 °C)<br />DC-13 60000 cycles 14.4 W 24 V 158 °F (70 °C)<br />DC-13 40000 cycles 48 W 24 V -13…140 °F (-25…60 °C)<br />DC-13 40000 cycles 28.8 W 24 V 158 °F (70 °C)<br />DC-13 40000 cycles 40 W 48...60 V -13…140 °F (-25…60 °C)<br />DC-13 40000 cycles 24 W 48...60 V 158 °F (70 °C)<br />DC-13 100000 cycles 15 W 100...125 V -13…140 °F (-25…60 °C)<br />DC-13 40000 cycles 15 W 100...125 V 158 °F (70 °C) |
Status LED | 1 LED (Green) RUN<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) ERR<br />1 LED (Red) I/O | Net Weight | 0.373 lb(US) (0.169 kg) |
IP Degree of Protection | IP20 | Environmental characteristic | Gas resistant class Gx<br />Gas resistant class 3C4<br />Dust resistant class 3S4<br />Sand resistant class 3S4<br />Salt resistant level 2<br />Mold growth resistant class 3B2<br />Fungal spore resistant class 3B2 |
Dielectric strength | 1780 V AC 50/60 Hz 1 min | Vibration resistance | 3 gn |
Shock resistance | 30 gn | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Ambient Air Temperature for Operation | -13…158 °F (-25…70 °C) | Relative humidity | 0…95 % 140 °F (60 °C) without condensation |
Protective treatment | Conformal coating | Operating altitude | 0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor |
Specifications may be subject to change without notice