Product Model
BMXDRA1605

Selling Points
- 1The BMXDRA1605 offers 16 relay outputs conforming to EN/IEC 61131-2 standards, ensuring reliable control over various devices.
- 2Handles 24 V DC (19-30 V) and 240 V AC (19-264 V), making it versatile for diverse industrial environments.
- 3Includes output overload protection, discharge diodes for DC outputs, RC circuits for AC outputs, and ZNO surge limiters for enhanced safety.
- 4Boasts an impressive Mean Time Between Failures (MTBF) of 1,357,810 hours, ensuring consistent performance in demanding environments.
- 5Consumes just 79 mA at 3.3 V DC, contributing to energy efficiency and reducing operational costs.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon X80 | Product or Component Type | Discrete output module |
Discrete output number | 16 EN/IEC 61131-2 | Discrete output type | Relay |
Discrete output voltage | 24...48 V 19...60 V DC<br />24...240 V 19…264 V AC | [Ith] conventional free air thermal current | 2 A |
Insulation resistance | > 10 MOhm 500 V DC | Power dissipation in W | 3 W |
Response time on output | < 8 ms activation<br />< 10 ms deactivation | Typical current consumption | 100 mA 3.3 V DC<br />95 mA 24 V DC |
MTBF reliability | 2100000 H | Output overload protection | Use 1 fast blow fuse per channel or group of channel |
Output overvoltage protection | Use discharge diode on each output DC<br />Use RC circuit on each output AC<br />Use ZNO surge limiter on each output AC | Output short-circuit protection | Use 1 fast blow fuse per channel or group of channel |
Minimum switching current | 1 mA 5 V DC | Electrical durability | AC-15 100000 cycles 240 VA 200 V 0.7)<br />AC-15 100000 cycles 120 VA 200 V 0.35)<br />AC-12 100000 cycles 200 VA 100 V<br />AC-12 100000 cycles 80 VA 48 V<br />AC-12 100000 cycles 50 VA 24 V<br />AC-15 100000 cycles 120 VA 100 V<br />AC-15 100000 cycles 120 VA 24 V<br />AC-15 100000 cycles 120 VA 48 V<br />DC-12 100000 cycles 24 W 24 V<br />DC-13 100000 cycles 10 W 24 V<br />DC-13 100000 cycles 10 W 48 V<br />AC-15 300000 cycles 72 VA 200 V 0.7)<br />AC-15 300000 cycles 36 VA 200 V 0.35)<br />AC-12 300000 cycles 200 VA 200 V<br />AC-12 300000 cycles 80 VA 100 V<br />AC-12 300000 cycles 50 VA 48 V<br />AC-15 300000 cycles 36 VA 100 V<br />AC-15 300000 cycles 72 VA 100 V<br />AC-15 300000 cycles 36 VA 48 V<br />AC-15 300000 cycles 72 VA 48 V<br />AC-15 300000 cycles 36 VA 24 V<br />AC-15 300000 cycles 72 VA 24 V<br />DC-13 300000 cycles 3 W 24 V<br />DC-13 300000 cycles 3 W 48 V<br />DC-13 7000 cycles 24 W 24 V<br />DC-13 7000 cycles 24 W 48 V<br />DC-12 50000 cycles 24 W 48 V |
Status LED | 1 LED (Green) RUN<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) ERR<br />1 LED (Red) I/O | Net Weight | 0.33 lb(US) (0.15 kg) |
IP Degree of Protection | IP20 | Dielectric strength | 2000 V AC 50/60 Hz 1 min |
Vibration resistance | 3 gn | Shock resistance | 30 gn |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Relative humidity | 5…95 % 131 °F (55 °C) without condensation | Operating altitude | 0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor |