Product Model
BMXEHC0200

Selling Points
- 1High-Speed Counter Module: Supports up to 60,000 Hz counting frequency.
- 2Advanced Counter Functions: Includes loop (modulo) counting, width modulation, down counting, and more.
- 3Robust Design: IP20 rated for reliable operation in various environments.
- 4Versatile Inputs: Compatible with 19.2–30 V 2-wire/3-wire proximity sensors and incremental encoders.
- 5Configurable Outputs: Positive or negative discrete output logic for flexible application integration.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon M340 automation platform | Product or Component Type | Counter module |
Number of Channels | 2 | Maximum counting frequency | 60000 Hz |
Number of inputs | 6 | Input compatibility | 19.2…30 V 2-wire/3-wire proximity sensor<br /> incremental encoder with push-pull outputs, 10...30 V totem pole |
Input voltage | 24 V DC type 3 | Number of outputs | 2 |
Output voltage | 24 V DC | Counter functions | Loop (modulo) counting<br />Width modulation<br />Down counting<br />Measure time periods<br />Ratio count<br />Count events<br />32-bit counter counting<br />Frequency meter |
Cycle time | 1 ms | Isolation voltage | 1500 V 60 s |
input type | 3 auxiliary input<br />3 high speed | Input voltage limits | 30 V |
Input current | 2 mA at 11 V | Voltage state 1 guaranteed | 11...30 V |
Current state 1 guaranteed | >= 6 mA | Voltage state 0 guaranteed | < 5 V |
Current state 0 guaranteed | <= 1.5 mA | Discrete output logic | Positive or negative configurable |
Maximum output current | 2 A per module<br />0.5 A per output | Output voltage limits | 19.2...30 V |
Maximum load current | 1 A per module<br />0.5 A per output | Maximum leakage current | 0.1 mA at state 0 |
Maximum voltage drop | <3 V at state 1 | Output overload protection | Integrated |
Output short-circuit protection | 1.5 A integrated | Overlap time | 0.2 ms |
Electrical connection | 1 connector 10 pins for wiring auxiliary input and sensor power supply<br />1 connector 16 pins for wiring the sensors of counter 0<br />1 connector 16 pins for wiring the sensors of counter 1 | Current consumption | 200 mA 3.3 V DC bus<br />40 mA 24 V DC rack<br />80 mA 24 V DC sensor |
Module format | Standard | Net Weight | 0.247 lb(US) (0.112 kg) |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Relative Humidity | 10…95 % without condensation |
IP Degree of Protection | IP20 | Directives | 2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility |
Protective treatment | TC |
Specifications may be subject to change without notice