Product Model
BMXMSP0200

Selling Points
- 1Designed for robust performance in PLC applications.
- 2Configurable for various input types, including proximity sensors.
- 3Compatible with standard 24 V DC power supply.
- 4Only 4.3 mA per input, reducing energy costs.
- 5Equipped with 2 connectors of 28 pins for seamless integration.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon X80 | Product or Component Type | PTO module |
Number of Channels | 2 | Number of inputs | 4 |
Discrete input type | Current sink yes origin input IEC 61131-2 type 3<br />Current sink yes proximity input and limit switch input IEC 61131-2 type 3<br />Current sink or source counter in position input IEC 61131-2 type 3<br />Current sink or source drive ready, emergency input IEC 61131-2 type 3 | Input compatibility | 2-wire/3-wire proximity sensor 19.2…30 V IEC 947-5-2 |
Output compatibility | Signal converter (USIC)<br />RS422, 7 mA input<br />Source input, 5 V to 24 V | Output frequency | 200 kHz <1.6 ft (0.5 m) with USIC and VW3M8210R05<br />100 kHz <16.4 ft (5 m) with the normal source input circuit<br />200 kHz <32.8 ft (10 m) with the RS422 compatible circuits |
Operating threshold | > 12 V no error supply voltage<br />> 8 V error supply voltage | Input voltage | 24 V DC |
Input current | 4.3 mA | Voltage state 1 guaranteed | >= 11 V |
Current consumption | 35 mA 24 V DC preactuator<br />150 mA 3.3 V DC typical<br />200 mA 3.3 V DC maximum | Current state 1 guaranteed | >= 2 mA |
Voltage state 0 guaranteed | 5 V | Current state 0 guaranteed | <= 1.5 mA |
Response time | < 200 µs for position completed input and drive ready input<br />< 60 µs for origin input and proximity input | Number of outputs | 1 pulse output<br />2 auxiliary output |
Preactuator voltage detection threshold | < 8 V error preactuator voltage auxiliary output<br />< 8 V no error preactuator voltage auxiliary output<br />> 14 V error preactuator voltage pulse output<br />> 14 V no error preactuator voltage pulse output | Output voltage | 24 V DC |
Output voltage limits | 19...30 V | Discrete output current | 50 mA |
Current per channel | 0.4 A | Maximum leakage current | 0.05 mA at state 0 |
[Ures] residual voltage | 0.15 V at state 1 | Response time on output | 1.2...1.5 ms on appearance<br />1.2...1.5 ms on disappearance |
Load impedance ohmic | 15000 Ohm | Output overload protection | By current limiter and electronic circuit breaker |
Output short-circuit protection | By current limiter and electronic circuit breaker | Reverse polarity protection | By reverse mounting diode on output<br />Integrated on input |
Insulation between channels | No insulated | Insul btwn prim and second | 1500 Vrms |
Insulation resistance | > 10 MOhm | Local signalling | for module operating (RUN) 1 LED (green)<br /> for external fault (I/O) 1 LED (red)<br /> for internal fault, module failure (ERR) 1 LED (red)<br /> for download (DL) 1 LED (green)<br /> for channel status (CH00) 8 LEDs (green)<br /> for channel status (CH01) 8 LEDs (green) |
Electrical connection | 2 connectors 28 pins | Module format | Standard |
Product certifications | CE<br />UL<br />CSA<br />RCM<br />EAC<br />Merchant Navy<br />ATEX zone 2/22<br />IECEx zone 2/22 | Ambient Air Temperature for Operation | -13…158 °F (-25…70 °C) |
Derating factor | Without | Directives | 2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility<br />2014/34/EU - ATEX directive |
Standards | EN/IEC 61131-2<br />EN/IEC 61010-2-201<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201<br />IACS E10<br />EN/IEC 61000-6-5, interface type 1 and type 2<br />EN/IEC 61850-3, location G<br />EN/IEC 60079-0 | Environmental characteristic | Hazardous location class I division 2 |
Specifications may be subject to change without notice