schneider GV2ME223

Selling Points

  • 1Thermal-Magnetic Protection: Ensures reliable motor protection with both thermal and magnetic tripping mechanisms.
  • 23P Configuration: Designed for 3-phase motor applications, providing comprehensive protection.
  • 320-25 A Current Range: Adjustable current range from 20 to 25 A for customizable settings.
  • 4Spring Terminals: Easy and secure connection with spring terminals for efficient installation.
  • 5IEC 60947 Compliance: Meets international standards for safety and performance, ensuring high-quality protection.
Product Details
GV2ME223
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2ME
Device Application
Motor protection
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2<br />AC-3 IEC 60947-4-1<br />AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-4-1
Motor power kW
11 kW 400/415 V AC 50/60 Hz<br />15 kW 500 V AC 50/60 Hz
Breaking capacity
50 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2<br />15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2<br />6 kA Icu 440 V AC 50/60 Hz IEC 60947-2<br />4 kA Icu 500 V AC 50/60 Hz IEC 60947-2<br />3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2<br />40 % 400/415 V AC 50/60 Hz IEC 60947-2<br />50 % 440 V AC 50/60 Hz IEC 60947-2<br />75 % 500 V AC 50/60 Hz IEC 60947-2<br />75 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Push-button
Line Rated Current
25 A
Thermal protection adjustment range
20…25 A IEC 60947-4-1
Magnetic tripping current
388.3 A
[Ith] conventional free air thermal current
25 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Phase failure sensitivity
Yes IEC 60947-4-1
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In<br />100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Fixing mode
35 mm symmetrical DIN rail clipped<br />Panel screwed with adaptor plate)
Mounting position
Horizontal<br />Vertical
Width
1.8 in (45 mm)
Height
4.0 in (101 mm)
Depth
3.09 in (78.5 mm)
Net Weight
0.62 lb(US) (0.28 kg)
color
Dark grey
Standards
EN/IEC 60947-2<br />EN/IEC 60947-4-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />IEC/EN 60335-2-40:Annex JJ<br />IEC/EN 60335-1:Clause 30.2
Product Certifications
CCC<br />UL<br />CSA<br />EAC<br />ATEX<br />LROS (Lloyds register of shipping)<br />BV<br />RINA<br />DNV-GL<br />UKCA
IK degree of protection
IK04
IP degree of protection
IP20 IEC 60529
Climatic withstand
IACS E10
Ambient Air Temperature for Storage
-40…176 °F (-40…80 °C)
Fire resistance
1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation
-4…140 °F (-20…60 °C)
Mechanical robustness
Shocks 30 Gn for 11 ms<br />Vibrations 5 Gn, 5...150 Hz
Operating altitude
6561.68 ft (2000 m)

Specifications may be subject to change without notice