schneider GV2P21

Selling Points

  • 1Thermal-Magnetic Protection: Ensures reliable protection against overloads and short circuits.
  • 2High Breaking Capacity: Icu 50 kA at 400 V for robust motor control.
  • 3Rotary Knob Actuator: Guaranteed for 100,000 cycles AC-3 415 V start-stop control.
  • 4Compact Design: Dimensions 45 mm W x 89 mm D x 97 mm H, suitable for various industrial settings.
  • 5Advanced Features: Ambient compensated bi-metallic reset type and IP20/IK04 enclosure for enhanced safety.
Product Details
GV2P21
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2P
Device Application
Motor protection
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2<br />AC-3 IEC 60947-4-1<br />AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-4-1
Motor power kW
9 kW 400/415 V AC 50/60 Hz<br />11 kW 500 V AC 50/60 Hz<br />18.5 kW 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2<br />50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2<br />20 kA Icu 440 V AC 50/60 Hz IEC 60947-2<br />10 kA Icu 500 V AC 50/60 Hz IEC 60947-2<br />4 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2<br />50 % 400/415 V AC 50/60 Hz IEC 60947-2<br />75 % 440 V AC 50/60 Hz IEC 60947-2<br />75 % 500 V AC 50/60 Hz IEC 60947-2<br />100 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Rotary handle
Line Rated Current
23 A
Thermal protection adjustment range
17…23 A IEC 60947-4-1
Magnetic tripping current
341 A
[Ith] conventional free air thermal current
23 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Phase failure sensitivity
Yes IEC 60947-4-1
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In<br />100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail clipped<br />Panel screwed with 2 x M4 screws)
Mounting position
Horizontal<br />Vertical
Width
1.8 in (45 mm)
Height
3.5 in (89 mm)
Depth
3.8 in (97 mm)
color
Dark grey
Standards
EN/IEC 60947-2<br />EN/IEC 60947-4-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />IEC/EN 60335-2-40:Annex JJ<br />IEC/EN 60335-1:Clause 30.2
Product Certifications
CCC<br />UL<br />CSA<br />EAC<br />ATEX<br />LROS (Lloyds register of shipping)<br />BV<br />RINA<br />DNV-GL<br />UKCA
IK degree of protection
IK04
IP degree of protection
IP20 IEC 60529
Climatic withstand
IACS E10
Ambient Air Temperature for Storage
-40…176 °F (-40…80 °C)
Fire resistance
1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation
-4…140 °F (-20…60 °C)
Mechanical robustness
Shocks 30 Gn for 11 ms<br />Vibrations 5 Gn, 5...150 Hz
Operating altitude
6561.68 ft (2000 m)

Specifications may be subject to change without notice