Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Harmony GTU | Product or Component Type | Flat screen |
Terminal type | Touchscreen display | [Us] rated supply voltage | 12...24 V DC power supply |
Supply voltage limits | 10.8…28.8 V | Power Consumption in W | 22 W |
Inrush current | 30 A | Integrated connection type | USB 2.0 type A |
Touchscreen resolution | 1024 x 1024 | Pixel resolution | 1024 x 768 |
Display size | 15 inch | Aspect ratio | 4:3 |
Display type | Colour TFT LCD | Display Resolution | 1024 x 768 pixels XGA |
Display colour | 16 million colours | Backlight lifespan | 50000 hours |
Touch panel | Multi touch analogue resistive | Provided equipment | 1 flash card |
Function Available | Brightness sensor | Type of cooling | Natural convection |
Type of Installation | Indoor installation | cut-out dimensions | 383.5 (+ 1/- 0) x 282.5 (+ 1/- 0) mm |
Width | 15.6 in (397 mm) | Height | 11.7 in (296 mm) |
Depth | 2.6 in (67 mm) | Net Weight | 9.9 lb(US) (4.5 kg) |
IP degree of protection | Front panel IP66 | NEMA degree of protection | NEMA 4X front panel |
Standards | UL 508 | Product certifications | CE<br />UKCA<br />UKEX |
Ambient air temperature for operation | 32…140 °F (0…60 °C) EN 61131-2 | Ambient air temperature for storage | -4…140 °F (-20…60 °C) |
Relative Humidity | 10…90 % non-condensing | Operating altitude | 6561.68 ft (2000 m) |
Vibration resistance | 3.5 mm constant amplitude 5…9 Hz) EN/IEC 61131-2 | Shock resistance | 147 m/s²EN/IEC 61131-2 |
Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2 |
Specifications may be subject to change without notice