Selling Points

  • 1Advanced Digital I/O: 14 regular digital inputs and 8 regular digital outputs.
  • 2Fast I/O Capabilities: 2 fast digital inputs and outputs for high-speed applications.
  • 3Compact Design: Mount via a 22 mm hole, no need for a rectangular cut-out.
  • 4Green Premium Compliance: Meets Schneider Electric’s Green Premium standards for environmental performance.
  • 5Integrated Communications: Supports serial, Ethernet, USB, and CANopen master for seamless connectivity.
Product Details
HMISAC
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony SCU
Product or Component Type
Controller
Device presentation
Basic element
Supply
External source
[Us] rated supply voltage
24 V 20.4…28.8 V)DC
Immunity to microbreaks
10 ms
Inrush current
30 A
Power consumption in W
15 W
Local signalling
No indicator
Number of pages
Limited by internal memory capacity
Software Designation
SoMachine
Operating System
Harmony
Processor name
CPU RISC
Processor frequency
333 MHz
Memory description
Flash NAND, 128 MB<br />Internal data storage FRAM, 128 kB<br />Application run DRAM, 128 MB
Integrated connection type
1 serial link - RJ45 - RS232/RS485 <= 115.2 kbits/s)<br />1 Ethernet TCP/IP - RJ45<br />1 USB 2.0 type mini B<br />1 USB 2.0 type A<br /> CANopen master bus - SUB-D 9
Realtime clock
Built-in
Downloadable protocols
Modbus<br />Modbus TCP/IP<br />CANopen
Fixing mode
By 1 nut Ø 22 mm 1...6 mm thick panel
Enclosure Material
PC/PBT
Shock resistance
147 m/s² 11 ms on DIN rail)IEC 60068-2-27<br />294 m/s² 6 ms on panel mounting)IEC 60068-2-27
Vibration resistance
+/- 3.5 mm 5…9 Hz) IEC 60068-2-6<br />1 gn 9…150 Hz) IEC 60068-2-6
Electromagnetic compatibility
Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2<br />Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to IEC 61000-4-3<br />Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 1 kV (between analogue I/O and operating voltage) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 2 kV (relay wires) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 1 kV (Ethernet line) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 1 kV (COM line) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 1 kV (CAN line) conforming to IEC 61000-4-4<br />Surge immunity test - test level: 2 kV (power supply (common mode)) conforming to IEC 61000-4-5<br />Surge immunity test - test level: 1 kV (power supply (differential mode)) conforming to IEC 61000-4-5<br />Surge immunity test - test level: 1 kV common mode (digital I/O) conforming to IEC 61000-4-5<br />Surge immunity test - test level: 0.5 kV differential mode (digital I/O) conforming to IEC 61000-4-5<br />Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6<br />Conducted emission - test level: 150 kHz...30 MHz conforming to EN 55011<br />Radiated emission - test level: 30 MHz...1 GHz conforming to EN 55011
Discrete input number
2 fast input (normal mode) IEC 61131-2 Type 1<br />14 digital input IEC 61131-2 Type 1
Discrete input voltage
24 V DC sink or source (positive/negative)
Number of common point
1 fast input (HSC mode)<br />2 digital input
Discrete input current
7.83 mA fast input<br />5 mA digital
input impedance
4.7 kOhm<br />2.81 kOhm
Sensor power supply
15…28.8 V DC >= 15 V >= 5 mA <= 5 V <= 1.5 mA<br />15…28.8 V DC >= 15 V >= 2.5 mA <= 5 V <= 1 mA
Configurable filtering time
0 ms no filter none)<br />0.004...0.04 ms bounce filter latch/event and cumulative filter by step Nx0.5ms (64>=N>=2))<br />3...12 ms integrator none/run/stop)
Maximum input frequency
100 kHz fast input (encoder mode) A/B<br />100 kHz fast input single phase<br />100 kHz fast input pulse/direction
Maximum cable distance between devices
Shielded cable <32.8 ft (10 m) fast input<br />Shielded cable <328.08 ft (100 m) digital input<br />Unshielded cable <164.04 ft (50 m) digital input
Connection pitch
0.1 in (3.5 mm)
Overvoltage protection
With
Isolation between channels and internal logic
500 V DC
Isolation between channels
None
Discrete output number
2 fast output (normal mode) source<br />8 digital output source
Discrete output voltage
24 V DC 19.2...28.8 V)transistor<br />24 V DC 5...30 V)relay<br />220 V AC 100...250 V)relay
Input/output number
2 fast input FI0...FI1<br />14 digital input DI0...DI13<br />2 fast output FQ0...FQ1<br />8 digital output DQ0...DQ7
Discrete output current
2 A 4 A)5 ms opening contact digital output<br />2 A 4 A)2 ms closing contact digital output<br />300 mA2 ms fast output (normal mode)<br />50 mA2 ms fast output (PWM or PTO mode)
Insulation resistance
> 10 MOhm between the I/O and internal logic<br />> 10 MOhm between power supply and earth
Maximum output frequency
100 kHz fast output (PTO mode)<br />1 kHz fast output (PWM mode)
Absolute accuracy error
+/- 0.1 % of full scale cyclic ratio 1...99% fast output (PWM or PTO mode)<br />1 % of full scale cyclic ratio 1...99% fast output (PWM or PTO mode)<br />+/- 5 % of full scale cyclic ratio 10...90% fast output (PWM or PTO mode)<br />+/- 10 % of full scale cyclic ratio 20...80% fast output (PWM or PTO mode)<br />+/- 15 % of full scale cyclic ratio 30...70% fast output (PWM or PTO mode)
Height
1.99 in (50.65 mm)
Width
5.04 in (128 mm)
Depth
4.02 in (102 mm)
Net Weight
0.791 lb(US) (0.359 kg)
Standards
FCC Class A<br />ANSI/ISA 12-12-01<br />UL 508<br />IEC 61000-6-2<br />EN 61131-2<br />CSA C22.2 No 213 Class I Division 2
Product Certifications
GOST<br />C-tick<br />KCC<br />cULus 508<br />cULus CSA 22-2 No 142<br />cUL 1604 Class 1 Division 2
marking
CE
Ambient Air Temperature for Operation
32…122 °F (0…50 °C)
Ambient Air Temperature for Storage
-4…140 °F (-20…60 °C)
Relative humidity
5…85 % without condensation
Operating altitude
<= 6561.68 ft (2000 m)
Storage altitude
0.0000000000…32808.4 ft (0…10000 m)
Maximum pressure
800...1114 hPa
IP degree of protection
IP20 IEC 60529 rear panel)<br />IP65 IEC 60529 front panel)
NEMA degree of protection
NEMA 4X front panel
Pollution degree
2 IEC 60664
Environmental characteristic
Corrosive gas free

Specifications may be subject to change without notice