Product Model
LC1D093Q7

Selling Points
- 1Reliable Motor Control: The LC1D093Q7 TeSys Deca Contactor ensures reliable motor control in AC-3 applications up to 440V and 9A.
- 2Efficient Operation: Designed for efficient operation, this contactor minimizes energy loss and maximizes system performance.
- 3Compact Design: The compact design makes it easy to integrate into various industrial settings, saving space and enhancing flexibility.
- 4High-Quality Components: Built with high-quality components, the LC1D093Q7 guarantees long-lasting performance and minimal maintenance.
- 5Compliance with Standards: Meets international standards (IEC 60947-5-1 and IEC 60947-4-1) for safe and reliable operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range | TeSys | Range of Product | TeSys Deca |
Product or Component Type | Contactor | Device short name | LC1D |
Contactor application | Motor control<br />Resistive load | Utilisation category | AC-1<br />AC-4<br />AC-3 |
Poles description | 3P | [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz<br />Power circuit <= 300 V DC |
[Ie] rated operational current | 9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />20 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit | [Uc] control circuit voltage | 380 V AC 50/60 Hz |
Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)<br />4 kW at 380...400 V AC 50/60 Hz (AC-3)<br />4 kW at 415...440 V AC 50/60 Hz (AC-3)<br />5.5 kW at 500 V AC 50/60 Hz (AC-3)<br />5.5 kW at 660...690 V AC 50/60 Hz (AC-3)<br />2.2 kW at 400 V AC 50/60 Hz (AC-4) | Maximum Horse Power Rating | 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors<br />2 hp at 200/208 V AC 50/60 Hz for 3 phase motors<br />2 hp at 230/240 V AC 50/60 Hz for 3 phase motors<br />5 hp at 460/480 V AC 50/60 Hz for 3 phase motors<br />7.5 hp at 575/600 V AC 50/60 Hz for 3 phase motors<br />0.33 hp at 115 V AC 50/60 Hz for 1 phase motors |
compatibility code | LC1D | Pole contact composition | 3 NO |
Protective cover | With | [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for signalling circuit<br />16 A (at 140 °F (60 °C)) for power circuit |
Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947<br />140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1 | Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 105 A 104 °F (40 °C) - 10 s for power circuit<br />210 A 104 °F (40 °C) - 1 s for power circuit<br />30 A 104 °F (40 °C) - 10 min for power circuit<br />61 A 104 °F (40 °C) - 1 min for power circuit<br />100 A - 1 s for signalling circuit<br />120 A - 500 ms for signalling circuit<br />140 A - 100 ms for signalling circuit | Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1<br />25 A gG at <= 690 V coordination type 1 for power circuit<br />20 A gG at <= 690 V coordination type 2 for power circuit |
Average impedance | 2.5 mOhm - Ith 16 A 50 Hz for power circuit | Power dissipation per pole | 1.56 W AC-1<br />0.2 W AC-3 |
[Ui] rated insulation voltage | Power circuit 690 V IEC 60947-4-1<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL | Overvoltage category | III |
Pollution degree | 3 | [Uimp] rated impulse withstand voltage | 6 kV IEC 60947 |
Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 | Mechanical durability | 15 Mcycles |
Electrical durability | 0.6 Mcycles 25 A AC-1 <= 440 V<br />2 Mcycles 9 A AC-3 <= 440 V | Control circuit type | AC 50/60 Hz |
Coil technology | Without built-in suppressor module | Control circuit voltage limits | 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz<br />0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz<br />1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz |
Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))<br />70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C)) | Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
Heat dissipation | 2…3 W at 50/60 Hz | Operating time | 12...22 ms closing<br />4...19 ms opening |
Maximum operating rate | 3600 cyc/h 140 °F (60 °C) | Connections - terminals | Power circuit: spring terminals 1 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end<br />Power circuit: spring terminals 2 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: spring terminals 1 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: spring terminals 2 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end |
Auxiliary contact composition | 1 NO + 1 NC | Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1 |
Signalling circuit frequency | 25...400 Hz | Minimum switching voltage | 17 V for signalling circuit |
Minimum switching current | 5 mA for signalling circuit | Insulation resistance | > 10 MOhm for signalling circuit |
Non-overlap time | 1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact | Mounting Support | Rail<br />Plate |
Standards | CSA C22.2 No 14<br />EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />UL 508 | Product Certifications | CSA<br />LROS (Lloyds register of shipping)<br />GL<br />DNV<br />RINA<br />BV<br />CCC<br />UL<br />GOST |
IP degree of protection | IP20 front face IEC 60529 | Protective treatment | THIEC 60068-2-30 |
Climatic withstand | IACS E10 exposure to damp heat<br /> IEC 60947-1 Annex Q category D exposure to damp heat | Permissible ambient air temperature around the device | -40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating |
Operating altitude | 0...9842.52 ft (0...3000 m) | Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
Flame retardance | V1 conforming to UL 94 | Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor open 10 Gn for 11 ms) <br />Shocks contactor closed 15 Gn for 11 ms) |
Height | 3.1 in (80 mm) | Width | 1.8 in (45 mm) |
Depth | 3.4 in (86 mm) | Net Weight | 0.71 lb(US) (0.32 kg) |
Specifications may be subject to change without notice