schneider LC1D1506L7

Selling Points

  • 1High-Performance AC Switching: The LC1D1506L7 contactor is designed for reliable and efficient AC switching, ensuring stable operation in various industrial applications.
  • 2Compact Design: With a compact design, this contactor is easy to install and integrate into complex systems, reducing installation time and space requirements.
  • 3Wide Voltage Range: Capable of handling voltages up to 440V and currents up to 150A, making it versatile for a wide range of industrial applications.
  • 4Fast Operation Times: Features fast closing and opening times of 20-35 ms and 40-75 ms respectively, ensuring quick response times in dynamic systems.
  • 5Durable Construction: Built with durable materials and designed for long-lasting performance, reducing the need for frequent replacements and maintenance.
Product Details
LC1D1506L7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-1<br />AC-4<br />AC-3<br />AC-3e
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 1000 V AC 25...400 Hz<br />Power circuit <= 300 V DC
[Ie] rated operational current
200 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit<br />150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />150 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
200 V AC 50/60 Hz
Motor power kW
40 kW at 220...230 V AC 50/60 Hz (AC-3)<br />75 kW at 380...400 V AC 50/60 Hz (AC-3)<br />80 kW at 415...440 V AC 50/60 Hz (AC-3)<br />90 kW at 500 V AC 50/60 Hz (AC-3)<br />100 kW at 660...690 V AC 50/60 Hz (AC-3)<br />75 kW at 1000 V AC 50/60 Hz (AC-3)<br />22 kW at 400 V AC 50/60 Hz (AC-4)<br />40 kW at 220...230 V AC 50/60 Hz (AC-3e)<br />75 kW at 380...400 V AC 50/60 Hz (AC-3e)<br />80 kW at 415...440 V AC 50/60 Hz (AC-3e)<br />90 kW at 500 V AC 50/60 Hz (AC-3e)<br />100 kW at 660...690 V AC 50/60 Hz (AC-3e)<br />75 kW at 1000 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating
40 hp at 200/208 V AC 50/60 Hz for 3 phase motors<br />50 hp at 230/240 V AC 50/60 Hz for 3 phase motors<br />100 hp at 460/480 V AC 50/60 Hz for 3 phase motors<br />125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1<br />1660 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 104 °F (40 °C) - 10 min for power circuit<br />580 A 104 °F (40 °C) - 1 min for power circuit<br />1200 A 104 °F (40 °C) - 10 s for power circuit<br />1400 A 104 °F (40 °C) - 1 s for power circuit<br />100 A - 1 s for signalling circuit<br />120 A - 500 ms for signalling circuit<br />140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1<br />315 A gG at <= 690 V coordination type 1 for power circuit<br />250 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole
24 W AC-1<br />13.5 W AC-3<br />13.5 W AC-3e
[Ui] rated insulation voltage
Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Power circuit 1000 V IEC 60947-4-1<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
8 Mcycles
Electrical durability
0.85 Mcycles 150 A AC-3 <= 440 V<br />1 Mcycles 200 A AC-1 <= 440 V<br />0.85 Mcycles 150 A AC-3e <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.3...0.5 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.15 Uc -40…131 °F (-40…55 °C) operational AC 50/60 Hz<br />1...1.15 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz
Inrush power in VA
280…350 VA 60 Hz cos phi 0.9 (at 68 °F (20 °C))<br />280…350 VA 50 Hz cos phi 0.9 (at 68 °F (20 °C))
Hold-in power consumption in VA
2…18 VA 60 Hz cos phi 0.9 (at 68 °F (20 °C))<br />2…18 VA 50 Hz cos phi 0.9 (at 68 °F (20 °C))
Heat dissipation
3…4.5 W at 50/60 Hz
Operating time
20...35 ms closing<br />40...75 ms opening
Maximum operating rate
1200 cyc/h at 60 °C
Connections - terminals
Control circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)<br />Power circuit: lugs-ring terminals - external diameter: 1.0 in (25 mm)<br />Power circuit: bars 1 - busbar cross section: 5 x 25 mm
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m) lugs-ring terminals flat Ø 6 mm M3.5<br />Control circuit 10.6 lbf.in (1.2 N.m) lugs-ring terminals Philips No 2 M3.5<br />Power circuit 106.2 lbf.in (12 N.m) lugs-ring terminals hexagonal 0.5 in (13 mm) M8<br />Power circuit 106.2 lbf.in (12 N.m) bars hexagonal 0.5 in (13 mm) M8<br />Control circuit 10.6 lbf.in (1.2 N.m) lugs-ring terminals pozidriv No 2 M3.5
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact
Mounting Support
Plate<br />Rail
Standards
CSA C22.2 No 14<br />EN 60947-4-1<br />IEC 60947-4-1<br />IEC 60335-1:Clause 30.2<br />IEC 60335-2-40:Annex JJ<br />UL 60335-2-40:Annex JJ<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1
Product Certifications
UL<br />CCC<br />CSA<br />CE<br />UKCA<br />Marine<br />EAC
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor closed 15 Gn for 11 ms) <br />Shocks contactor open 6 Gn for 11 ms)
Height
6.2 in (158 mm)
Width
4.7 in (120 mm)
Depth
5.4 in (136 mm)
Net Weight
5.5 lb(US) (2.5 kg)

Specifications may be subject to change without notice