schneider LC1D2586B7

Selling Points

  • 1Highly Integrated Design: Perfectly integrates into control systems for various applications.
  • 2AC-1 Utilization Category: Rated for operational voltage of 690VAC at 25Hz to 400Hz and 300VDC for power circuit.
  • 340A Power Rating: Handles up to 40A at ≤440VAC for power circuit.
  • 424 V AC Coil: Operates with a 24 V AC coil for efficient control.
  • 5Durable Construction: IP2x front face conforming to IEC 60529 standard protection rating.
Product Details
LC1D2586B7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1<br />AC-3<br />AC-3e<br />AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz<br />Power circuit <= 300 V DC
[Ie] rated operational current
40 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
24 V AC 50/60 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit<br />40 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1<br />450 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
450 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
240 A 104 °F (40 °C) - 10 s for power circuit<br />380 A 104 °F (40 °C) - 1 s for power circuit<br />50 A 104 °F (40 °C) - 10 min for power circuit<br />120 A 104 °F (40 °C) - 1 min for power circuit<br />100 A - 1 s for signalling circuit<br />120 A - 500 ms for signalling circuit<br />140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1<br />63 A gG at <= 690 V coordination type 1 for power circuit<br />40 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
2 mOhm - Ith 40 A 50 Hz for power circuit
Power dissipation per pole
3.2 W AC-1
[Ui] rated insulation voltage
Power circuit 690 V IEC 60947-4-1<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
15 Mcycles
Electrical durability
1.4 Mcycles 40 A AC-1 <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz<br />0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz<br />1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA
70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))<br />70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
2…3 W at 50/60 Hz
Operating time
12...22 ms closing<br />4...19 ms opening
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)<br />Power circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5<br />Power circuit 15.9 lbf.in (1.8 N.m) lugs-ring terminals flat Ø 8 mm M3.5<br />Power circuit 15.9 lbf.in (1.8 N.m) lugs-ring terminals Philips No 2 M3.5
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact
Mounting Support
Plate<br />Rail
Standards
CSA C22.2 No 14<br />EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />UL 508
Product Certifications
BV<br />CSA<br />CCC<br />UL<br />RINA<br />GOST<br />DNV<br />GL<br />LROS (Lloyds register of shipping)
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat<br /> IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-76…176 °F (-60…80 °C) storage<br />-40…140 °F (-40…60 °C) operation<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor closed 15 Gn for 11 ms) <br />Shocks contactor open 8 Gn for 11 ms)
Height
3.6 in (91 mm)
Width
1.8 in (45 mm)
Depth
3.9 in (99 mm)
Net Weight
0.937 lb(US) (0.425 kg)

Specifications may be subject to change without notice