schneider LC1D40A6MD

Selling Points

  • 1High-Performance Motor Control: The LC1D40A6MD TeSys Deca Contactor is designed for high-performance motor control applications, ensuring reliable operation in AC-3 environments.
  • 240A Capacity: With a rated operational current of 40A at ≤440V AC, this contactor is suitable for a wide range of power circuit applications.
  • 3220V DC Standard Coil: Equipped with a 220V DC standard coil, this contactor offers flexibility in control circuit configurations.
  • 4Safety and Reliability: Compliant with EN/ISO 13849-1 standards, the LC1D40A6MD ensures high safety reliability levels, including B10d = 1369863 cycles with nominal load.
  • 5Mechanical Durability: Built to last, the contactor has a mechanical durability of 10 million cycles, ensuring long-term operation in demanding environments.
Product Details
LC1D40A6MD
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-1<br />AC-4<br />AC-3
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz<br />Power circuit <= 300 V DC
[Ie] rated operational current
60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit<br />40 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage
220 V DC
Motor power kW
18.5 kW at 380...400 V AC 50/60 Hz (AC-3)<br />11 kW at 220...230 V AC 50/60 Hz (AC-3)<br />22 kW at 415...440 V AC 50/60 Hz (AC-3)<br />22 kW at 500 V AC 50/60 Hz (AC-3)<br />30 kW at 660...690 V AC 50/60 Hz (AC-3)<br />9 kW at 400 V AC 50/60 Hz (AC-4)
Maximum Horse Power Rating
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors<br />10 hp at 230/240 V AC 50/60 Hz for 3 phase motors<br />30 hp at 575/600 V AC 50/60 Hz for 3 phase motors<br />10 hp at 200/208 V AC 50/60 Hz for 3 phase motors<br />3 hp at 115 V AC 50/60 Hz for 1 phase motors<br />30 hp at 460/480 V AC 50/60 Hz for 3 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit<br />60 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1<br />800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
320 A 104 °F (40 °C) - 10 s for power circuit<br />720 A 104 °F (40 °C) - 1 s for power circuit<br />72 A 104 °F (40 °C) - 10 min for power circuit<br />165 A 104 °F (40 °C) - 1 min for power circuit<br />100 A - 1 s for signalling circuit<br />120 A - 500 ms for signalling circuit<br />140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1<br />80 A gG at <= 690 V coordination type 1 for power circuit<br />80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole
2.4 W AC-3<br />5.4 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL<br />Power circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Electrical durability
0.7 Mcycles 60 A AC-1 <= 440 V<br />1.5 Mcycles 40 A AC-3 <= 440 V
Control circuit type
DC standard
Coil technology
Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC<br />0.75...1.25 Uc -40…140 °F (-40…60 °C) operational DC<br />1...1.25 Uc 140…158 °F (60…70 °C) operational DC
Inrush power in W
19 W 68 °F (20 °C))
Hold-in power consumption in W
7.4 W 68 °F (20 °C)
Operating time
50 ±15 % ms closing<br />20 ±20 % ms opening
Time constant
34 ms
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)<br />Power circuit: lugs-ring terminals - external diameter: 0.6 in (16.5 mm)
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5<br />Power circuit 53.1 lbf.in (6 N.m) lugs-ring terminals hexagonal 0.4 in (10 mm) M6
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact
Mounting Support
Rail<br />Plate
Standards
CSA C22.2 No 14<br />EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />UL 508
Product Certifications
GOST<br />CSA<br />UL<br />CCC
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat<br /> IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor closed 15 Gn for 11 ms) <br />Shocks contactor open 10 Gn for 11 ms)
Height
4.8 in (122 mm)
Width
2.2 in (55 mm)
Depth
4.7 in (120 mm)
Net Weight
2.039 lb(US) (0.925 kg)

Specifications may be subject to change without notice