schneider LC1D40G6

Selling Points

  • 1High Power Rating: 30 HP at 575/600 VAC for robust motor control.
  • 2Versatile Mounting: Can be mounted on DIN rail or directly to a panel.
  • 3Reliable Performance: Meets UL, CSA, IEC, and other international safety standards.
  • 4Energy Efficiency: Designed with TeSys D technology for reduced energy consumption.
  • 5Comprehensive Accessories: Extensive line of accessories available for easy integration into control systems.
Product Details
LC1D40G6
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-2<br />AC-1<br />AC-3<br />AC-4<br />AC-3e
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit<br />40 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />40 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
120 V AC 60 Hz
Motor power kW
18.5 kW at 380...400 V AC 50/60 Hz<br />22 kW at 500 V AC 50/60 Hz<br />30 kW at 660...690 V AC 50/60 Hz<br />11 kW at 220...230 V AC 50/60 Hz<br />22 kW at 1000 V AC 50/60 Hz<br />22 kW at 415 V AC 50/60 Hz<br />22 kW at 440 V AC 50/60 Hz
Maximum Horse Power Rating
10 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to CSA<br />10 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to UL<br />10 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to CSA<br />10 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to UL<br />3 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA<br />3 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL<br />30 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to CSA<br />30 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to UL<br />30 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to CSA<br />30 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to UL<br />5 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA<br />5 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit<br />60 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for control circuit conforming to IEC 60947-5-1<br />800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
800 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-1<br />80 A gG at <= 690 V coordination type 1 for power circuit<br />80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole
5.4 W AC-1<br />2.4 W AC-3<br />2.4 W AC-3e
[Ui] rated insulation voltage
Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1
Overvoltage category
III
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6000000 cycles
Control circuit type
AC 60 Hz
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.85...1.1 Uc 140 °F (60 °C) operational AC 60 Hz<br />0.3...0.6 Uc 140 °F (60 °C) drop-out AC 60 Hz
Inrush power in VA
140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
4…5 W at 50/60 Hz for control circuit
Operating time
12...26 ms closing<br />4...19 ms opening
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminal 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: solid with cable end<br />Power circuit: screw clamp terminal 2 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: solid with cable end<br />Power circuit: screw clamp terminal 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminal 2 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminal 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminal 2 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible with cable end
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 6 mm<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 8 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mirror contact 1 NC IEC 60947-4-1<br />Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Minimum switching voltage
17 V for control circuit
Minimum switching current
5 mA for control circuit
Insulation resistance
> 10 MOhm for control circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts
Mounting Support
Rail<br />Plate
Standards
EN 60947-5-1<br />IEC 60947-4-1<br />UL 508<br />CSA C22.2 No 14<br />EN 60947-4-1<br />IEC 60947-5-1
Product Certifications
GL<br />BV<br />DNV<br />LROS (Lloyds register of shipping)<br />RINA<br />UL<br />CCC<br />CSA<br />GOST<br />UKCA<br />CB
IP degree of protection
IP2X IEC 60529<br />IP2X VDE 0106
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
23…140 °F (-5…60 °C)<br />-40…158 °F (-40…70 °C) at Uc
Operating altitude
9842.52 ft (3000 m) without derating
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor opened 10 Gn for 11 ms) <br />Shocks contactor closed 15 Gn for 11 ms) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz)
Height
5.0000000000 in (127 mm)
Width
3.0 in (75 mm)
Depth
4.7 in (119 mm)
Net Weight
3.09 lb(US) (1.4 kg)

Specifications may be subject to change without notice