schneider LC1D40GD

Selling Points

  • 1High-Performance Motor Control: Designed to control and provide overload protection to motors rated up to 100 hp at 480 VAC.
  • 2Efficient Coil Design: Features a 125 VDC coil with up to 80% less consumption than standard AC or DC coils.
  • 3Easy Maintenance: Simplifies maintenance services with 90% less references needed due to its TeSys D green design.
  • 4Versatile Mounting Options: Can be panel mounted with screws or DIN rail mounted for flexible installation.
  • 5Robust Specifications: Includes built-in auxiliary contacts, IP20 finger-safe terminals, and a high-fault short circuit current rating.
Product Details
LC1D40GD
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys D
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-1<br />AC-2<br />AC-4<br />AC-3
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
40 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
125 V DC
Motor power kW
18.5 kW at 380...400 V AC 50 Hz<br />22 kW at 500 V AC 50 Hz<br />30 kW at 660...690 V AC 50 Hz<br />11 kW at 220...230 V AC 50 Hz<br />22 kW at 415 V AC 50 Hz<br />22 kW at 440 V AC 50 Hz<br />22 kW at 1000 V AC 50 Hz
Maximum Horse Power Rating
3 hp at 115 V AC 60 Hz for 1 phase motors<br />5 hp at 230/240 V AC 60 Hz for 1 phase motors<br />10 hp at 200/208 V AC 60 Hz for 3 phase motors<br />10 hp at 230/240 V AC 60 Hz for 3 phase motors<br />30 hp at 460/480 V AC 60 Hz for 3 phase motors<br />30 hp at 575/600 V AC 60 Hz for 3 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit<br />60 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
250 A DC for control circuit conforming to IEC 60947-5-1<br />800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
800 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-1<br />80 A gG at <= 690 V coordination type 1 for power circuit<br />80 A gG at <= 690 V coordination type 2 for power circuit
Power dissipation per pole
5.4 W AC-1<br />2.4 W AC-3
[Ui] rated insulation voltage
Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1
Overvoltage category
III
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10000000 cycles
Control circuit type
DC standard
Coil technology
Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC<br />0.75...1.25 Uc -40…140 °F (-40…60 °C) operational DC<br />1...1.25 Uc 140…158 °F (60…70 °C) operational DC
Inrush power in W
19 W 68 °F (20 °C))
Hold-in power consumption in W
7.4 W 68 °F (20 °C)
Rated operational power in W
12 W 125 V DC-13 10000000 cycles - control circuit<br />38 W 125 V DC-13 3000000 cycles - control circuit<br />76 W 125 V DC-13 1000000 cycles - control circuit
Operating time
20 ms opening<br />50 ms closing
Time constant
34 ms
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: rigid<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: rigid<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible with cable end
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw terminal flat Ø 6 to Ø 8 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Minimum switching voltage
17 V for control circuit
Minimum switching current
5 mA for control circuit
Insulation resistance
> 10 MOhm for control circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts
Mounting Support
Plate<br />Rail
Standards
IEC 60947-4-1<br />EN 60947-4-1<br />UL 508<br />CSA C22.2 No 14<br />EN 60947-5-1<br />IEC 60947-5-1
Product Certifications
LROS (Lloyds register of shipping)<br />RINA<br />CCC<br />CSA<br />GL<br />BV<br />DNV<br />UL<br />GOST
IP degree of protection
IP2X IEC 60529<br />IP2X VDE 0106
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-76…176 °F (-60…80 °C) storage<br />-40…140 °F (-40…60 °C) operation<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor opened 10 Gn) <br />Shocks contactor closed 15 gn) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz)
Height
5.0000000000 in (127 mm)
Width
3.3 in (85 mm)
Depth
6.9 in (176 mm)
Net Weight
4.817 lb(US) (2.185 kg)

Specifications may be subject to change without notice