Selling Points

  • 1High durability with 6 million operations at no load and 1.45 million operations with load.
  • 2Supports rated current of 80A in AC-1 and 50A in 440Vac AC-3 applications.
  • 3Designed for DIN rail mounting with a net width of 55 mm and IP20 degree of protection.
  • 4Includes 1 normally open (NO) and 1 normally closed (NC) auxiliary contact for versatile control.
  • 5Rated active power up to 33kW in 660-690Vac AC-3 applications, suitable for various industrial settings.
Product Details
LC1D506K7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-2<br />AC-4<br />AC-1<br />AC-3
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
100 V AC 50/60 Hz
Motor power kW
22 kW at 380...400 V AC 50 Hz<br />25 kW at 415 V AC 50 Hz<br />30 kW at 440 V AC 50 Hz<br />30 kW at 500 V AC 50 Hz<br />33 kW at 660...690 V AC 50 Hz<br />15 kW at 220...230 V AC 50 Hz<br />30 kW at 1000 V AC 50 Hz
Maximum Horse Power Rating
3 hp at 115 V AC 60 Hz for 1 phase motors<br />7.5 hp at 230/240 V AC 60 Hz for 1 phase motors<br />15 hp at 200/208 V AC 60 Hz for 3 phase motors<br />15 hp at 230/240 V AC 60 Hz for 3 phase motors<br />40 hp at 460/480 V AC 60 Hz for 3 phase motors<br />40 hp at 575/600 V AC 60 Hz for 3 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit<br />80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
900 A at 440 V for power circuit conforming to IEC 60947<br />140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity
900 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-1<br />100 A gG at <= 690 V coordination type 1 for power circuit<br />100 A gG at <= 690 V coordination type 2 for power circuit
Power dissipation per pole
3.7 W AC-3<br />9.6 W AC-1
[Ui] rated insulation voltage
Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1
Overvoltage category
III
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6000000 cycles
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz<br />0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz<br />1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA
140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
4…5 W at 50/60 Hz for control circuit
Operating time
4...19 ms opening<br />12...26 ms closing
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: lugs - external diameter: 0.3 in (8 mm)<br />Power circuit: lugs - external diameter: 0.6 in (16 mm)
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) lugs Philips No 2<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs flat Ø 6 mm<br />Power circuit 22.1 lbf.in (2.5 N.m) lugs flat Ø 8 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Terminals description ISO n°1
(13-14)NO<br />(A1-A2)CO<br />(21-22)NC
Minimum switching voltage
17 V for control circuit
Minimum switching current
5 mA for control circuit
Insulation resistance
> 10 MOhm for control circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts
Mounting Support
Plate<br />Rail
Standards
IEC 60947-5-1<br />IEC 60947-4-1<br />EN 60947-4-1<br />UL 508<br />CSA C22.2 No 14<br />EN 60947-5-1
Product Certifications
CCC<br />BV<br />UL<br />GOST<br />LROS (Lloyds register of shipping)<br />GL<br />RINA<br />CSA<br />DNV
IP degree of protection
IP2X IEC 60529<br />IP2X VDE 0106
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-76…176 °F (-60…80 °C) storage<br />-40…140 °F (-40…60 °C) operation<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor opened 10 Gn) <br />Shocks contactor closed 15 gn) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz)
Height
5.0000000000 in (127 mm)
Width
3.0 in (75 mm)
Depth
4.7 in (119 mm)
Net Weight
3.09 lb(US) (1.4 kg)

Specifications may be subject to change without notice