schneider LC1D50A6Q7

Selling Points

  • 1High-Performance Contactor: The LC1D50A6Q7 supports up to 50A at 440V AC-3 applications.
  • 2DIN Rail Mounting: Designed for easy installation on DIN rail with a net width of 55 mm.
  • 3IP20 Protection: Offers a degree of protection rated at IP20, ensuring reliable operation in various environments.
  • 4Versatile Power Handling: Rated active power reaches up to 33kW in 660-690Vac AC-3 applications.
  • 5Advanced Durability: Rated for 6 million operations at no load and 1.45 million operations with load, ensuring long-lasting performance.
Product Details
LC1D50A6Q7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-1<br />AC-4<br />AC-3
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz<br />Power circuit <= 300 V DC
[Ie] rated operational current
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
380 V AC 50/60 Hz
Motor power kW
15 kW at 220...230 V AC 50/60 Hz (AC-3)<br />22 kW at 380...400 V AC 50/60 Hz (AC-3)<br />30 kW at 500 V AC 50/60 Hz (AC-3)<br />33 kW at 660...690 V AC 50/60 Hz (AC-3)<br />25 kW at 415 V AC 50/60 Hz (AC-3)<br />30 kW at 440 V AC 50/60 Hz (AC-3)<br />11 kW at 400 V AC 50/60 Hz (AC-4)
Maximum Horse Power Rating
3 hp at 115 V AC 50/60 Hz for 1 phase motors<br />7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors<br />15 hp at 200/208 V AC 50/60 Hz for 3 phase motors<br />15 hp at 230/240 V AC 50/60 Hz for 3 phase motors<br />40 hp at 460/480 V AC 50/60 Hz for 3 phase motors<br />40 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit<br />80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1<br />900 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
900 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
400 A 104 °F (40 °C) - 10 s for power circuit<br />810 A 104 °F (40 °C) - 1 s for power circuit<br />84 A 104 °F (40 °C) - 10 min for power circuit<br />208 A 104 °F (40 °C) - 1 min for power circuit<br />100 A - 1 s for signalling circuit<br />120 A - 500 ms for signalling circuit<br />140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1<br />100 A gG at <= 690 V coordination type 1 for power circuit<br />100 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
3.7 W AC-3<br />9.6 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL<br />Power circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.45 Mcycles 50 A AC-3 <= 440 V<br />1.1 Mcycles 80 A AC-1 <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz<br />0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz<br />1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA
140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))<br />160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
4…5 W at 50/60 Hz
Operating time
4...19 ms opening<br />12...26 ms closing
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)<br />Power circuit: lugs-ring terminals - external diameter: 0.6 in (16.5 mm)
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5<br />Power circuit 53.1 lbf.in (6 N.m) lugs-ring terminals hexagonal 0.4 in (10 mm) M6
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact
Mounting Support
Plate<br />Rail
Standards
CSA C22.2 No 14<br />EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />UL 508
Product Certifications
UL<br />BV<br />CCC<br />GL<br />LROS (Lloyds register of shipping)<br />DNV<br />CSA<br />GOST<br />RINA
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat<br /> IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor closed 15 Gn for 11 ms) <br />Shocks contactor open 10 Gn for 11 ms)
Height
4.8 in (122 mm)
Width
2.2 in (55 mm)
Depth
4.7 in (120 mm)
Net Weight
1.885 lb(US) (0.855 kg)

Specifications may be subject to change without notice