schneider LC1D65004U5

Selling Points

  • 1High power handling with 80AMP capacity.
  • 2Compact design suitable for various industrial applications.
  • 3Reliable performance in 4POLE configuration.
  • 4Compatible with 440VOLT systems.
  • 5Available from trusted suppliers for quick delivery.
Product Details
LC1D65004U5
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <140 °F (60 °C)) AC AC-1 for power circuit
[Uc] control circuit voltage
240 V AC 50 Hz
Maximum Horse Power Rating
10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA<br />10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL<br />20 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to CSA<br />20 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to UL<br />20 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to CSA<br />20 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to UL<br />5 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA<br />5 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL<br />50 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to CSA<br />50 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to UL<br />50 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to CSA<br />50 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to UL
compatibility code
LC1D
Pole contact composition
4 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit<br />80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1000 A at 440 V for power circuit conforming to IEC 60947<br />140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-1<br />125 A gG at <= 690 V coordination type 1 for power circuit<br />125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
6.4 W AC-1
[Ui] rated insulation voltage
Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1
Overvoltage category
III
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6000000 cycles
Control circuit type
AC 50 Hz standard
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.3...0.6 Uc 140 °F (60 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc 140 °F (60 °C) operational AC 50 Hz<br />0.85...1.1 Uc 140 °F (60 °C) operational AC 60 Hz
Inrush power in VA
140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
4…5 W at 50/60 Hz for control circuit
Operating time
12...26 ms closing<br />4...19 ms opening
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Power circuit: screw clamp terminal 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end<br />Power circuit: screw clamp terminal 2 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 6 mm<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 8 mm<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal pozidriv No 2
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Minimum switching voltage
17 V for control circuit
Minimum switching current
5 mA for control circuit
Insulation resistance
> 10 MOhm for control circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts
Mounting Support
Rail<br />Plate
Standards
CSA C22.2 No 14<br />IEC 60947-5-1<br />IEC 60947-4-1<br />UL 508<br />EN 60947-4-1<br />EN 60947-5-1
Product Certifications
BV<br />CCC<br />GL<br />DNV<br />LROS (Lloyds register of shipping)<br />RINA<br />CSA<br />GOST<br />UL
IP degree of protection
IP2X IEC 60529<br />IP2X VDE 0106
Protective treatment
TH 3)IEC 60068
Permissible ambient air temperature around the device
23…140 °F (-5…60 °C)<br />-40…158 °F (-40…70 °C) at Uc
Operating altitude
9842.52 ft (3000 m) without derating
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor open 8 Gn for 11 ms) <br />Shocks contactor closed 10 Gn for 11 ms) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 3 Gn, 5...300 Hz)
Height
5.0000000000 in (127 mm)
Width
3.3 in (85 mm)
Depth
5.1 in (130 mm)
Net Weight
3.17 lb(US) (1.44 kg)

Specifications may be subject to change without notice