schneider LC1D656SW

Selling Points

  • 1High-Performance Rating: Rated for 65 AMP AC-3 and 80 AMP AC-1.
  • 2Versatile Motor Control: Handles up to 20 HP at 230V and 40 HP at 460V in three-phase motor applications.
  • 3Built-In Auxiliary Contacts: Includes 1 NO (normally open) and 1 NC (normally closed) base-mounted contacts.
  • 4Enhanced Safety Features: IP20 Finger-Safe Terminals ensure safety with terminals designed to meet North American and international standards.
  • 5Reliable Design: Proven design combined with reliable performance from TeSys D-line, suitable for industrial and commercial applications.
Product Details
LC1D656SW
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-4<br />AC-3<br />AC-3<br />AC-4
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
24 V AC 50/60 Hz
Motor power kW
37 kW at 500 V AC 50 Hz<br />37 kW at 660...690 V AC 50 Hz<br />18.5 kW at 220...230 V AC 50 Hz<br />30 kW at 415 V AC 50 Hz<br />37 kW at 1000 V AC 50 Hz<br />22 kW at 380...400 V AC 50 Hz (AC-3)<br />25 kW at 415 V AC 50 Hz (AC-3)
Maximum Horse Power Rating
20 hp at 200/208 V AC 60 Hz for 3 phase motors<br />20 hp at 230/240 V AC 60 Hz for 3 phase motors<br />40 hp at 460/480 V AC 60 Hz for 3 phase motors<br />50 hp at 575/600 V AC 60 Hz for 3 phase motors<br />3 hp at 115 V AC 60 Hz for 1 phase motors<br />7.5 hp at 230/240 V AC 60 Hz for 1 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit<br />80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
900 A at 440 V for power circuit conforming to IEC 60947<br />140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity
900 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
125 A gG at <= 690 V coordination type 2 for power circuit<br />10 A gG for control circuit conforming to IEC 60947-5-1<br />100 A gG at <= 690 V coordination type 1 for power circuit
Power dissipation per pole
3.7 W AC-3<br />9.6 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1<br />Control circuit 600 V CSA<br />Control circuit 600 V UL
Overvoltage category
III
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6000000 cycles
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
1...1.25 Uc 140…158 °F (60…70 °C) operational DC<br />0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
Inrush power in VA
140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
4…5 W at 50/60 Hz for control circuit
Operating time
4...19 ms opening<br />12...26 ms closing
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid
Tightening torque
Power circuit 22.1 lbf.in (2.5 N.m) lugs flat Ø 8 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs pozidriv No 2<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Minimum switching voltage
17 V for control circuit
Minimum switching current
5 mA for control circuit
Insulation resistance
> 10 MOhm for control circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts
Mounting Support
Rail<br />Plate
Standards
CSA C22.2 No 14<br />EN 60947-4-1<br />IEC 60947-4-1<br />IEC 60947-5-1
Product Certifications
CSA<br />DNV<br />LROS (Lloyds register of shipping)<br />GOST<br />GL<br />RINA<br />UL<br />CSA<br />DNV
IP degree of protection
IP2X IEC 60529<br />IP2X VDE 0106
Climatic withstand
IACS E10 exposure to damp heat<br /> IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-76…176 °F (-60…80 °C) storage<br />-40…140 °F (-40…60 °C) operation<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor opened 10 Gn) <br />Shocks contactor closed 15 gn)
Height
4.8 in (122 mm)
Width
2.2 in (55 mm)
Depth
4.7 in (120 mm)
Net Weight
3.09 lb(US) (1.4 kg)
Quantity per Set
Set of 10

Specifications may be subject to change without notice