LC1D65SW
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys D
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load<br />Resistive load
Utilisation category
AC-1<br />AC-4<br />AC-3<br />AC-1
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
65 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />65 A (at <140 °F (60 °C)) DC AC-3 for power circuit<br />80 A (at <140 °F (60 °C)) DC AC-1 for power circuit
[Uc] control circuit voltage
480 V DC
Motor power kW
30 kW at 380...400 V AC 50 Hz<br />37 kW at 500 V AC 50 Hz<br />37 kW at 660...690 V AC 50 Hz<br />18.5 kW at 220...230 V AC 50 Hz<br />30 kW at 415 V AC 50 Hz<br />37 kW at 1000 V AC 50 Hz
Maximum Horse Power Rating
10 hp at 230/240 V AC 60 Hz for 1 phase motors<br />20 hp at 200/208 V AC 60 Hz for 3 phase motors<br />20 hp at 230/240 V AC 60 Hz for 3 phase motors<br />40 hp at 460/480 V AC 60 Hz for 3 phase motors<br />50 hp at 575/600 V AC 60 Hz for 3 phase motors<br />5 hp at 115 V AC 60 Hz for 1 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
80 A (at 140 °F (60 °C)) for power circuit<br />10 A (at 140 °F (60 °C)) for control circuit
Irms rated making capacity
1000 A at 440 V DC for power circuit conforming to IEC 60947<br />1000 A at 440 V for power circuit conforming to IEC 60947<br />250 A DC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity
1000 kA at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
520 A 104 °F (40 °C) - 10 s for power circuit<br />900 A 104 °F (40 °C) - 1 s for power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 2 for power circuit<br />160 A gG at <= 690 V coordination type 1 for power circuit conforming to IEC 60947-5-1<br />125 A gG at <= 690 V coordination type 1 for power circuit<br />10 A gG for control circuit conforming to IEC 60947-5-1
Average impedance
1.5 Ohm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
6.4 W AC-1<br />6.3 W AC-3<br />9.6 W AC-1
[Ui] rated insulation voltage
Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL IEC 60947-1<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1<br />Power circuit 1000 V CSA IEC 60947-4-1<br />Control circuit 600 V CSA
Overvoltage category
III
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10000000 cycles
Control circuit type
DC standard
Coil technology
Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.75...1.25 Uc -40…140 °F (-40…60 °C) operational DC<br />1...1.25 Uc 140…158 °F (60…70 °C) operational DC<br />0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC
Inrush power in W
19 W 68 °F (20 °C))
Hold-in power consumption in W
7.4 W 68 °F (20 °C)
Heat dissipation
4…5 W at 50/60 Hz for control circuit
Operating time
50 ms closing<br />12...26 ms closing<br />4...19 ms opening
Maximum operating rate
3600 cyc/mn 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: rigid<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: rigid without cable end<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw terminal flat Ø 6 to Ø 8 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal pozidriv No 2<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mirror contact 1 NC IEC 60947-4-1<br />Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Minimum switching voltage
17 V for control circuit
Minimum switching current
5 mA for control circuit
Insulation resistance
> 10 MOhm for control circuit
Non-overlap time
1.5 ms on energisation between NC and NO contacts<br />1.5 ms on de-energisation between NC and NO contacts
Mounting Support
Rail<br />Rail
Standards
UL 508<br />EN 60947-4-1<br />EN 60947-5-1<br />CSA C22.2 No 14<br />IEC 60947-5-1
Product Certifications
RINA<br />LROS (Lloyds register of shipping)<br />CCC<br />GOST<br />UL<br />GL<br />BV<br />DNV<br />CSA
IP degree of protection
IP2X VDE 0106<br />IP2X IEC 60529
Protective treatment
TH 3)IEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-76…176 °F (-60…80 °C) storage<br />-40…140 °F (-40…60 °C) operation<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor closed 15 gn) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor opened 10 Gn)
Height
4.8 in (122 mm)
Width
2.8 in (70 mm)
Depth
4.6 in (118 mm)
Net Weight
4.817 lb(US) (2.185 kg)
Quantity per Set
Set of 1

Specifications may be subject to change without notice