Product Model
LC1D65X6

Selling Points
- 1High Power Rating: Handles up to 20 HP at 230V and 40 HP at 460V in three-phase motor applications.
- 2Reliable Performance: Includes an AC-rated coil for consistent performance and built-in auxiliary contacts for extended capability.
- 3Versatile Mounting: Available in screw panel-mount or DIN rail mount options, ensuring flexibility in installation.
- 4Safety Features: IP20 Finger-Safe Terminals designed to meet North American and international safety standards.
- 5Comprehensive Accessories: Compatible with a range of optional accessories including auxiliary contact blocks, surge suppressors, and overload relays for enhanced system integration.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range | TeSys | Range of Product | TeSys D |
Product or Component Type | Contactor | Device short name | LC1D |
Contactor application | Resistive load<br />Motor control | Utilisation category | AC-2<br />AC-1<br />AC-4<br />AC-3 |
Poles description | 3P | [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz |
[Ie] rated operational current | 80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit<br />65 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit | [Uc] control circuit voltage | 600 V AC 60 Hz |
Motor power kW | 30 kW at 440 V AC 50/60 Hz<br />30 kW at 380...400 V AC 50/60 Hz<br />37 kW at 500 V AC 50/60 Hz<br />37 kW at 660...690 V AC 50/60 Hz<br />18.5 kW at 220...230 V AC 50/60 Hz<br />30 kW at 415 V AC 50/60 Hz<br />37 kW at 1000 V AC 50/60 Hz | Maximum Horse Power Rating | 10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA<br />10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL<br />20 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to CSA<br />20 hp at 200/208 V AC 60 Hz for 3 phase motors conforming to UL<br />20 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to CSA<br />20 hp at 230/240 V AC 60 Hz for 3 phase motors conforming to UL<br />5 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA<br />5 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL<br />50 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to CSA<br />50 hp at 460/480 V AC 60 Hz for 3 phase motors conforming to UL<br />50 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to CSA<br />50 hp at 575/600 V AC 60 Hz for 3 phase motors conforming to UL |
compatibility code | LC1D | Pole contact composition | 3 NO |
Protective cover | With | [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for control circuit<br />80 A (at 140 °F (60 °C)) for power circuit |
Irms rated making capacity | 140 A AC for control circuit conforming to IEC 60947-5-1<br />1000 A at 440 V for power circuit conforming to IEC 60947 | Rated breaking capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
Associated fuse rating | 10 A gG for control circuit conforming to IEC 60947-5-1<br />125 A gG at <= 690 V coordination type 1 for power circuit<br />125 A gG at <= 690 V coordination type 2 for power circuit | Average impedance | 1 mOhm - Ith 80 A 50 Hz for power circuit |
Power dissipation per pole | 6.4 W AC-1 | [Ui] rated insulation voltage | Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1 |
Overvoltage category | III | [Uimp] rated impulse withstand voltage | 8 kV IEC 60947 |
Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 | Mechanical durability | 6000000 cycles |
Control circuit type | AC 60 Hz | Coil technology | Without built-in bidirectional peak limiting diode suppressor |
Control circuit voltage limits | 0.3...0.6 Uc 140 °F (60 °C) drop-out AC 50/60 Hz<br />0.85...1.1 Uc 140 °F (60 °C) operational AC 60 Hz | Inrush power in VA | 140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C)) |
Hold-in power consumption in VA | 13 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) | Heat dissipation | 4…5 W at 50/60 Hz for control circuit |
Operating time | 12...26 ms closing<br />4...19 ms opening | Maximum operating rate | 3600 cyc/h 140 °F (60 °C) |
Connections - terminals | Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: solid with cable end<br />Power circuit: connector 2 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: solid with cable end<br />Power circuit: connector 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible without cable end<br />Power circuit: connector 2 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: connector 1 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 2 0.004…0.05 in² (2.5…35 mm²) - cable stiffness: flexible with cable end | Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 6 mm<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 8 mm |
Auxiliary contact composition | 1 NO + 1 NC | Auxiliary contacts type | Mirror contact 1 NC IEC 60947-4-1<br />Mechanically linked 1 NO + 1 NC IEC 60947-5-1 |
Terminals description ISO n°1 | (13-14)NO<br />(A1-A2)CO<br />(21-22)NC | Minimum switching voltage | 17 V for control circuit |
Minimum switching current | 5 mA for control circuit | Insulation resistance | > 10 MOhm for control circuit |
Non-overlap time | 1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts | Mounting Support | Rail<br />Plate |
Standards | EN 60947-5-1<br />IEC 60947-4-1<br />CSA C22.2 No 14<br />EN 60947-4-1<br />UL 508<br />IEC 60947-5-1 | Product Certifications | UL<br />LROS (pending)<br />RINA<br />CCC<br />CSA<br />GOST<br />BV<br />GL<br />DNV |
IP degree of protection | IP2X IEC 60529<br />IP2X VDE 0106 | Climatic withstand | IACS E10 exposure to damp heat |
Permissible ambient air temperature around the device | -76…176 °F (-60…80 °C) storage<br />-40…140 °F (-40…60 °C) operation<br />140…158 °F (60…70 °C) with derating | Operating altitude | 9842.52 ft (3000 m) without derating |
Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 | Flame retardance | V1 conforming to UL 94 |
Mechanical robustness | Shocks contactor opened 10 Gn) <br />Shocks contactor closed 15 gn) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) | Height | 5.0000000000 in (127 mm) |
Width | 3.0 in (75 mm) | Depth | 4.7 in (119 mm) |
Net Weight | 3.09 lb(US) (1.4 kg) |
Specifications may be subject to change without notice