schneider LC1D80004F7

Selling Points

  • 1High-Performance Motor Control: Designed to control and provide overload protection to motors rated up to 100 hp at 480 VAC or 125 hp at 600 VAC.
  • 2Energy Efficiency: TeSys D green contactor reduces energy consumption by up to 50% with the associated TeSys LR9D electronic overload relay.
  • 3Durability and Reliability: High fault short circuit current ratings and built-in auxiliary contacts ensure reliability and flexibility in various applications.
  • 4Easy Maintenance: Simplified maintenance with 90% less references needed, reducing downtime and increasing overall efficiency.
  • 5Comprehensive Specifications: Includes built-in auxiliary contacts, screw clamp terminals, and an open enclosure for easy integration into control systems.
Product Details
LC1D80004F7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1<br />AC-3<br />AC-3e<br />AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 300 V DC 25...400 Hz<br />Power circuit <= 690 V AC
[Ie] rated operational current
125 A (at <140 °F (60 °C)) at <= 1000 V AC AC-1 for power circuit<br />80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit<br />55 A (at <140 °F (60 °C)) at <= 400 V AC AC-4 for power circuit
[Uc] control circuit voltage
110 V AC 50/60 Hz
Motor power kW
22 kW at 220...230 V AC 50/60 Hz<br />37 kW at 380...400 V AC 50/60 Hz<br />45 kW at 660...690 V AC 50/60 Hz<br />55 kW at 500 V AC 50/60 Hz<br />45 kW at 415...440 V AC 50/60 Hz
compatibility code
LC1D
Pole contact composition
4 NO
Protective cover
With
[Ith] conventional free air thermal current
125 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
640 A 104 °F (40 °C) - 10 s for power circuit<br />990 A 104 °F (40 °C) - 1 s for power circuit<br />135 A 104 °F (40 °C) - 10 min for power circuit<br />320 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
200 A gG at <= 690 V coordination type 1 for power circuit<br />160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
12.5 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Power circuit 1000 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
4 Mcycles
Electrical durability
0.8 Mcycles 125 A AC-1 <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.85...1.1 Uc -40…131 °F (-40…55 °C) operational AC 60 Hz<br />0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc -40…131 °F (-40…55 °C) operational AC 50 Hz<br />1...1.1 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz
Inrush power in VA
245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))<br />245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
6…10 W at 50/60 Hz
Operating time
20...35 ms closing<br />6...20 ms opening
Maximum operating rate
3600 cyc/h at 60 °C
Connections - terminals
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible without cable end<br />Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 2 0.006…0.02 in² (4…16 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: solid without cable end<br />Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: solid without cable end
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2<br />Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm<br />Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Mounting Support
Plate<br />Rail
Standards
EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />CSA C22.2 No 14<br />UL 60947-4-1<br />IEC 60335-2-40:Annex JJ<br />UL 60335-2-40:Annex JJ<br />IEC 60335-1:Clause 30.2
Product Certifications
CCC<br />UL<br />CB Scheme<br />CSA<br />CE<br />UKCA<br />Marine<br />EAC
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) <br />Shocks contactor open 8 Gn for 11 ms) <br />Vibrations contactor closed 3 Gn, 5...300 Hz) <br />Shocks contactor closed 10 Gn for 11 ms)
Height
5.0000000000 in (127 mm)
Width
3.8 in (96 mm)
Depth
4.9 in (125 mm)
Net Weight
3.88 lb(US) (1.76 kg)

Specifications may be subject to change without notice