schneider LC1D95L6

Selling Points

  • 1Up to 3600 cycles/hour at 60°C.
  • 2Designed for heavy-duty applications with a contractual warranty of 18 months.
  • 3Compatible with both plate and rail mounting supports.
  • 4Meets EN/ISO 13849-1 standards with a B10d value of 1.3 Mcycles for nominal load.
  • 5Low power dissipation per pole (12.5 W AC-1, 7.2 W AC-3).
Product Details
LC1D95L6
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-3e<br />AC-4<br />AC-1
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
95 A (at <140 °F (60 °C)) at <= 440 V AC-3 for power circuit<br />125 A (at <140 °F (60 °C)) at <= 1000 V AC-1 for power circuit
[Uc] control circuit voltage
200 V AC 60 Hz
Motor power kW
25 kW at 220...230 V AC 50 Hz (AC-3)<br />45 kW at 380...400 V AC 50 Hz (AC-3)<br />45 kW at 415...440 V AC 50 Hz (AC-3)<br />55 kW at 500 V AC 50 Hz (AC-3)<br />45 kW at 660...690 V AC 50 Hz (AC-3)<br />15 kW at 400 V AC 50 Hz (AC-4)<br />25 kW at 220...230 V AC 50 Hz (AC-3e)<br />45 kW at 380...400 V AC 50 Hz (AC-3e)<br />45 kW at 415...440 V AC 50 Hz (AC-3e)<br />55 kW at 500 V AC 50 Hz (AC-3e)<br />45 kW at 660...690 V AC 50 Hz (AC-3e)
Maximum Horse Power Rating
7.5 hp at 115 V AC 60 Hz for 1 phase motors<br />15 hp at 230/240 V AC 60 Hz for 1 phase motors<br />25 hp at 200/208 V AC 60 Hz for 3 phase motors<br />30 hp at 230/240 V AC 60 Hz for 3 phase motors<br />60 hp at 460/480 V AC 60 Hz for 3 phase motors<br />60 hp at 575/600 V AC 60 Hz for 3 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit<br />125 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1100 A at 440 V AC for power circuit conforming to IEC 60947<br />140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
1100 A 104 °F (40 °C) - 1 s for power circuit<br />800 A 104 °F (40 °C) - 10 s for power circuit<br />400 A 104 °F (40 °C) - 1 min for power circuit<br />135 A 104 °F (40 °C) - 10 min for power circuit<br />140 A - 100 ms for signalling circuit<br />120 A - 500 ms for signalling circuit<br />100 A - 1 s for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1<br />160 A gG at <= 690 V coordination type 2 for power circuit<br />200 A gG at <= 690 V coordination type 1 for power circuit
Average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
12.5 W AC-1<br />7.2 W AC-3
[Ui] rated insulation voltage
Power circuit 1000 V IEC 60947-4-1<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL
Overvoltage category
III
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Electrical durability
1.2 Mcycles 95 A AC-3<br />1.3 Mcycles 125 A AC-1
Control circuit type
AC 60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 60 Hz<br />0.85...1.1 Uc -40…131 °F (-40…55 °C) operational AC 60 Hz<br />1...1.1 Uc 131…158 °F (55…70 °C) operational AC 60 Hz
Inrush power in VA
220 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
22 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
6…10 W at 60 Hz for control circuit
Operating time
20...35 ms closing<br />6...20 ms opening
Maximum operating rate
3600 cyc/h at 60 °C
Connections - terminals
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: rigid<br />Power circuit: screw terminals 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: rigid<br />Power circuit: screw terminals 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 2 0.006…0.02 in² (4…16 mm²) - cable stiffness: flexible with cable end
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal Philips No 2<br />Power circuit 106.2 lbf.in (12 N.m) screw terminal flat Ø 6 to Ø 8 mm<br />Power circuit 106.2 lbf.in (12 N.m) screw terminal hex (Allen key) 0.2 in (4 mm)<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminal pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts
Mounting Support
Plate<br />Rail
Standards
EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />CSA C22.2 No 14<br />UL 60947-4-1<br />IEC 60335-2-40:Annex JJ<br />UL 60335-2-40:Annex JJ<br />IEC 60335-1:Clause 30.2
Product Certifications
CCC<br />UL<br />CB Scheme<br />CSA<br />CE<br />UKCA<br />Marine<br />EAC
IP degree of protection
IP20 IEC 60529
Protective treatment
TH 3)IEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor opened 8 Gn for 11 ms) <br />Shocks contactor closed 10 Gn for 11 ms) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 3 Gn, 5...300 Hz)
Height
5.0000000000 in (127 mm)
Width
3.3 in (85 mm)
Depth
5.1 in (130 mm)
Net Weight
3.55 lb(US) (1.61 kg)

Specifications may be subject to change without notice