schneider LC1D95U7

Selling Points

  • 1High-Performance Motor Control: Designed to control motors up to 60 HP at 460V and 30 HP at 230V.
  • 2Robust Construction: Built with 95 AMP AC-3 and 125 AMP AC-1 ratings, ensuring reliable operation in demanding applications.
  • 3Versatile Mounting Options: Compatible with both screw clamp terminals and DIN rail mounting, offering flexibility in installation.
  • 4Enhanced Safety Features: Includes 1 NO and 1 NC base-mounted contacts, with optional LADN auxiliary contacts for added safety.
  • 5Comprehensive Protection: Compatible with LRD33 thermal overload relays for complete motor protection, ensuring safe operation in various environments.
Product Details
LC1D95U7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-3<br />AC-3e<br />AC-4<br />AC-1
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
95 A (at <140 °F (60 °C)) at <= 440 V AC-3 for power circuit<br />125 A (at <140 °F (60 °C)) at <= 1000 V AC-1 for power circuit<br />95 A (at <140 °F (60 °C)) at <= 440 V AC-3e for power circuit
[Uc] control circuit voltage
240 V AC 50/60 Hz
Motor power kW
25 kW at 220...230 V AC 50 Hz (AC-3)<br />45 kW at 380...400 V AC 50 Hz (AC-3)<br />45 kW at 415...440 V AC 50 Hz (AC-3)<br />55 kW at 500 V AC 50 Hz (AC-3)<br />45 kW at 660...690 V AC 50 Hz (AC-3)<br />15 kW at 400 V AC 50 Hz (AC-4)<br />25 kW at 220...230 V AC 50 Hz (AC-3e)<br />45 kW at 380...400 V AC 50 Hz (AC-3e)<br />45 kW at 415...440 V AC 50 Hz (AC-3e)<br />55 kW at 500 V AC 50 Hz (AC-3e)<br />45 kW at 660...690 V AC 50 Hz (AC-3e)
Maximum Horse Power Rating
7.5 hp at 120 V AC 60 Hz for 1 phase motors<br />15 hp at 230/240 V AC 60 Hz for 1 phase motors<br />30 hp at 200/208 V AC 60 Hz for 3 phase motors<br />30 hp at 230/240 V AC 60 Hz for 3 phase motors<br />60 hp at 460/480 V AC 60 Hz for 3 phase motors<br />60 hp at 575/600 V AC 60 Hz for 3 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit<br />125 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1100 A at 440 V AC for power circuit conforming to IEC 60947<br />140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
1100 A 104 °F (40 °C) - 1 s for power circuit<br />800 A 104 °F (40 °C) - 10 s for power circuit<br />400 A 104 °F (40 °C) - 1 min for power circuit<br />135 A 104 °F (40 °C) - 10 min for power circuit<br />140 A - 100 ms for signalling circuit<br />120 A - 500 ms for signalling circuit<br />100 A - 1 s for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1<br />200 A gG at <= 690 V coordination type 1 for power circuit<br />160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
12.5 W AC-1<br />7.2 W AC-3<br />7.2 W AC-3e
[Ui] rated insulation voltage
Power circuit 1000 V IEC 60947-4-1<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
4 Mcycles
Electrical durability
1.2 Mcycles 95 A AC-3<br />1.3 Mcycles 125 A AC-1<br />1.2 Mcycles 95 A AC-3e
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.8...1.1 Uc -40…131 °F (-40…55 °C) operational AC 50 Hz<br />0.85...1.1 Uc -40…131 °F (-40…55 °C) operational AC 60 Hz<br />0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />1...1.1 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz
Inrush power in VA
245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))<br />245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
6…10 W at 50/60 Hz
Operating time
20...35 ms closing<br />6...20 ms opening
Maximum operating rate
3600 cyc/h at 60 °C
Connections - terminals
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible without cable end<br />Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 2 0.006…0.02 in² (4…16 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: solid without cable end<br />Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: solid without cable end
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2<br />Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm<br />Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)<br />Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact
Mounting Support
Rail<br />Plate
Standards
EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />CSA C22.2 No 14<br />UL 60947-4-1<br />IEC 60335-2-40:Annex JJ<br />UL 60335-2-40:Annex JJ<br />IEC 60335-1:Clause 30.2
Product Certifications
CCC<br />UL<br />CB Scheme<br />CSA<br />CE<br />UKCA<br />Marine<br />EAC
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) <br />Shocks contactor open 8 Gn for 11 ms) <br />Vibrations contactor closed 3 Gn, 5...300 Hz) <br />Shocks contactor closed 10 Gn for 11 ms)
Height
5.0000000000 in (127 mm)
Width
3.3 in (85 mm)
Depth
5.1 in (130 mm)
Net Weight
3.55 lb(US) (1.61 kg)

Specifications may be subject to change without notice