schneider LC1DFKF7

Selling Points

  • 112.5 kVAR at 400 V/50 Hz for efficient capacitor control.
  • 2Compatible with 110V 50/60Hz AC coil for wide application flexibility.
  • 3Includes 1NO+2NC instantaneous auxiliary contacts for reliable operation.
  • 4Front-mounted early make poles with pre-wired damping resistors for current limiting.
  • 5Built with high-quality materials for long-lasting performance in industrial settings.
Product Details
LC1DFKF7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys<br />TeSys Deca
Product name
TeSys LC1D.K<br />TeSys Deca
Product or Component Type
Capacitor duty contactor
Device short name
LC1DFK
Device Application
Control
Contactor application
Power factor correction
Utilisation category
AC-6b
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit 690 V AC 50/60 Hz
Reactive power rating
7 kvar 230 V AC 50 Hz 140 °F (60 °C)<br />12.5 kvar 400 V AC 50 Hz 140 °F (60 °C)<br />13 kvar 440 V AC 50 Hz 140 °F (60 °C)<br />21 kvar 690 V AC 50 Hz 140 °F (60 °C)
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
110 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 2 NC instantaneous
Electrical durability
300000 cycles 400 V<br />200000 cycles 690 V
Mounting Support
DIN rail<br />Plate
Standards
EN/IEC 60947-1<br />EN/IEC 60947-4-1<br />IEC 60335-1
Product Certifications
IECEE CB Scheme<br />UKCA
Connections - terminals
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminals 1 0.002…0.009 in² (1.5…6 mm²) - cable stiffness: solid<br />Power circuit: screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²) - cable stiffness: solid<br />Power circuit: screw clamp terminals 1 0.002…0.009 in² (1.5…6 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminals 2 0.002…0.009 in² (1.5…6 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminals 1 0.002…0.009 in² (1.5…6 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²) - cable stiffness: flexible with cable end
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals<br />Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals
Maximum operating rate
240 cyc/h
Auxiliary contacts type
Mechanically linked 1 NO + 2 NC IEC 60947-5-1
IP degree of protection
IP20 front face IEC 60529
Ambient Air Temperature for Operation
23…140 °F (-5…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Operating altitude
0...9842.52 ft (0...3000 m)
Height
4.5 in (115 mm)
Width
1.8 in (45 mm)
Depth
4.8 in (121 mm)
Net Weight
1.17 lb(US) (0.53 kg)

Specifications may be subject to change without notice