schneider LC1DGK11Q7

Selling Points

  • 1Designed for demanding applications, the LC1DGK11Q7 offers reliable operation.
  • 2Compatible with 400/415V 50Hz and 380V AC 50/60Hz coils.
  • 3Compact dimensions make it easy to integrate into various systems.
  • 4Part of Schneider Electric's Net Zero initiative, promoting circularity and recyclability.
  • 5Meets product certifications including UL CSA for added assurance.
Product Details
LC1DGK11Q7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Product name
TeSys LC1D.K<br />TeSys Deca
Product or Component Type
Capacitor duty contactor
Device short name
LC1DGK
Contactor application
Power factor correction
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit <= 690 V AC 50/60 Hz
Reactive power rating
16.7 kvar 400…440 V AC 50/60 Hz 131 °F (55 °C)<br />24 kvar 660…690 V AC 50/60 Hz 131 °F (55 °C)<br />8.5 kvar 220…240 V AC 50/60 Hz 131 °F (55 °C)
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
380 V AC 50/60 Hz
Auxiliary contact composition
1 NO + 1 NC
Mounting Support
Plate<br />Rail
Standards
VDE 0560<br />NF C 54-100<br />IEC 60070<br />IEC 60831
Product Certifications
UL<br />CSA
Connections - terminals
Power circuit: connector 1 0.004 in² (2.5 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 1 0.006 in² (4 mm²) - cable stiffness: solid with cable end<br />Power circuit: connector 2 0.002 in² (1.5 mm²) - cable stiffness: flexible with cable end<br />Power circuit: connector 2 0.006 in² (4 mm²) - cable stiffness: solid with cable end
Tightening torque
Power circuit 15.05 lbf.in (1.7 N.m) connector
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
IP degree of protection
IP2X IEC 60529<br />IP2X VDE 0106
Protective treatment
TH IEC 60068-2-30
Ambient Air Temperature for Operation
23…140 °F (-5…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Operating altitude
0...9842.52 ft (0...3000 m)
Height
5.1 in (130 mm)
Width
1.8 in (45 mm)
Depth
4.8 in (122 mm)
Net Weight
0.99 lb(US) (0.45 kg)

Specifications may be subject to change without notice