schneider LC1DT256BLS207

Selling Points

  • 1Designed for continuous operation with up to 3600 cycles/hour.
  • 2Equipped with a low-consumption 24V DC coil.
  • 3Suitable for resistive loads and motor control applications.
  • 4Front-mounted terminals provide IP20 protection.
  • 5Compatible with lugs-ring terminals and screw clamp connections.
Product Details
LC1DT256BLS207
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys<br />TeSys Deca
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1<br />AC-3<br />AC-3e<br />AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit<br />12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
Pole contact composition
4 NO
Protective cover
With
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1
Auxiliary contact composition
1 NO + 1 NC
[Ui] rated insulation voltage
Power circuit 690 V IEC 60947-4-1<br />Signalling circuit 690 V IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit<br />25 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947<br />140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1<br />40 A gG at <= 690 V coordination type 1 for power circuit<br />25 A gG at <= 690 V coordination type 2 for power circuit
Time constant
37 ms
Control circuit type
DC low consumption
Coil technology
With integral suppression device
Control circuit voltage limits
0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC<br />0.7...1.25 Uc -40…158 °F (-40…70 °C) operational DC
Average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole
1.56 W AC-1<br />0.36 W AC-3
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact
Operating time
77 ±15 % ms closing<br />25 ±20 % ms opening
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Inrush power in W
4 W 68 °F (20 °C))
Hold-in power consumption in W
4 W 68 °F (20 °C)
Insulation resistance
> 10 MOhm for signalling circuit
Connections - terminals
Control circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)<br />Power circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5<br />Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5<br />Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5<br />Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals pozidriv No 2 M3.5<br />Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals pozidriv No 2 M3.5
Mounting Support
Plate<br />Rail
Electrical durability
0.8 Mcycles 25 A AC-1 <= 440 V
Mechanical durability
30 Mcycles
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Operating altitude
0...9842.52 ft (0...3000 m)
compatibility code
LC1D
Standards
EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />EN 45545: R22 HL3<br />EN 45545: R26 HL3<br />DIN 5510-2
Product Certifications
IEC<br />CCC<br />EAC<br />UA<br />TR<br />UKCA<br />CB
Climatic withstand
IACS E10<br /> IEC 60947-1 Annex Q category D
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Height
3.3 in (85 mm)
Width
1.8 in (45 mm)
Depth
3.9 in (99 mm)
Net Weight
0.805 lb(US) (0.365 kg)
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor open 10 Gn for 11 ms) <br />Shocks contactor closed 15 Gn for 11 ms)