Product Model
LC1DT32BD

Selling Points
- 1Built with high-reliability components for consistent performance in industrial applications.
- 2Compact design for easy installation on DIN rail, ensuring space efficiency in control panels.
- 3Guarantees smooth operation with a low-level DC signal from a computer or PLC without needing an interposing relay.
- 4Operates effectively in ambient air temperatures ranging from -5°C to 60°C, making it suitable for various environments.
- 5Meets multiple international standards including IEC, UL, CSA, CCC, and Marine certifications for global compatibility and safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range | TeSys<br />TeSys Deca | Range of Product | TeSys Deca |
Product or Component Type | Contactor | Device short name | LC1D |
Contactor application | Resistive load | Utilisation category | AC-1<br />AC-3<br />AC-3e<br />AC-4 |
Poles description | 4P | [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz<br />Power circuit <= 300 V DC |
[Ie] rated operational current | 32 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit | [Uc] control circuit voltage | 24 V DC |
compatibility code | LC1D | Pole contact composition | 4 NO |
Protective cover | With | [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for signalling circuit<br />32 A (at 140 °F (60 °C)) for power circuit |
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1<br />250 A DC for signalling circuit conforming to IEC 60947-5-1<br />300 A at 440 V for power circuit conforming to IEC 60947 | Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 40 A 104 °F (40 °C) - 10 min for power circuit<br />84 A 104 °F (40 °C) - 1 min for power circuit<br />145 A 104 °F (40 °C) - 10 s for power circuit<br />240 A 104 °F (40 °C) - 1 s for power circuit<br />100 A - 1 s for signalling circuit<br />120 A - 500 ms for signalling circuit<br />140 A - 100 ms for signalling circuit | Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1<br />50 A gG at <= 690 V coordination type 1 for power circuit<br />35 A gG at <= 690 V coordination type 2 for power circuit |
Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit | Power dissipation per pole | 2.5 W AC-1 |
[Ui] rated insulation voltage | Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Signalling circuit 690 V IEC 60947-1<br />Signalling circuit 600 V CSA<br />Signalling circuit 600 V UL<br />Power circuit 690 V IEC 60947-4-1 | Overvoltage category | III |
Pollution degree | 3 | [Uimp] rated impulse withstand voltage | 6 kV IEC 60947 |
Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 | Mechanical durability | 30 Mcycles |
Electrical durability | 1 Mcycles 32 A AC-1 <= 440 V | Control circuit type | DC standard |
Coil technology | Built-in bidirectional peak limiting diode suppressor | Control circuit voltage limits | 0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC<br />0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC<br />1...1.25 Uc 140…158 °F (60…70 °C) operational DC |
Inrush power in W | 5.4 W 68 °F (20 °C)) | Hold-in power consumption in W | 5.4 W 68 °F (20 °C) |
Operating time | 20 ±20 % ms opening<br />63 ±15 % ms closing | Time constant | 28 ms |
Maximum operating rate | 3600 cyc/h at 60 °C | Connections - terminals | Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Power circuit: screw clamp terminals 1 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw clamp terminals 1 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw clamp terminals 1 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: solid without cable end<br />Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: solid without cable end |
Tightening torque | Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2<br />Power circuit 15.9 lbf.in (1.8 N.m) screw clamp terminals flat Ø 6 mm<br />Power circuit 15.9 lbf.in (1.8 N.m) screw clamp terminals Philips No 2<br />Power circuit 15.9 lbf.in (1.8 N.m) screw clamp terminals pozidriv No 2 | Auxiliary contact composition | 1 NO + 1 NC |
Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1 | Signalling circuit frequency | 25...400 Hz |
Minimum switching voltage | 17 V for signalling circuit | Minimum switching current | 5 mA for signalling circuit |
Insulation resistance | > 10 MOhm for signalling circuit | Non-overlap time | 1.5 ms on de-energisation between NC and NO contact<br />1.5 ms on energisation between NC and NO contact |
Mounting Support | Rail<br />Plate | Standards | CSA C22.2 No 14<br />EN 60947-4-1<br />EN 60947-5-1<br />IEC 60947-4-1<br />IEC 60947-5-1<br />UL 508<br />IEC 60335-1 |
Product Certifications | DNV<br />GL<br />CCC<br />LROS (Lloyds register of shipping)<br />RINA<br />BV<br />GOST<br />UL<br />CSA<br />CB | IP degree of protection | IP20 front face IEC 60529 |
Protective treatment | THIEC 60068-2-30 | Climatic withstand | IACS E10 exposure to damp heat<br /> IEC 60947-1 Annex Q category D exposure to damp heat |
Permissible ambient air temperature around the device | -40…140 °F (-40…60 °C)<br />140…158 °F (60…70 °C) with derating | Operating altitude | 0...9842.52 ft (0...3000 m) |
Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 | Flame retardance | V1 conforming to UL 94 |
Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) <br />Shocks contactor closed 15 Gn for 11 ms) <br />Shocks contactor open 8 Gn for 11 ms) | Height | 3.6 in (91 mm) |
Width | 1.8 in (45 mm) | Depth | 4.2 in (107 mm) |
Net Weight | 0.937 lb(US) (0.425 kg) |
Specifications may be subject to change without notice