Product Model
LC1F1154G622L

Selling Points
- 1Operates at 2400 cycles/hour withstanding harsh environments up to 55°C.
- 2Designed for AC-1 category, ensuring consistent operation in various conditions.
- 3Compatible with LX9, LX4, and LXE coils for diverse voltage requirements.
- 4Handles 200A with a rated operational current of 200A at 440V AC.
- 5Meets IEC 60947-4-1 standards for high reliability and safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | TeSys F | Product or Component Type | Contactor |
Device short name | LC1F | Contactor application | Resistive load |
Utilisation category | AC-1 | Poles description | 4P |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<br /> <= 460 V DC | [Uc] control circuit voltage | 120 V AC 60 Hz |
[Ie] rated operational current | 200 A (at <104 °F (40 °C)) at <= 440 V AC AC-1 | [Uimp] rated impulse withstand voltage | 8 kV |
[Ith] conventional free air thermal current | 200 A (at 104 °F (40 °C)) | Rated breaking capacity | 920 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current | 1100 A 104 °F (40 °C) - 10 s<br />640 A 104 °F (40 °C) - 30 s<br />520 A 104 °F (40 °C) - 1 min<br />400 A 104 °F (40 °C) - 3 min<br />320 A 104 °F (40 °C) - 10 min | Associated fuse rating | 125 A aM at <= 440 V<br />200 A gG at <= 440 V |
[Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C | Power dissipation per pole | 15 W AC-1 |
Overvoltage category | III | power pole contact composition | 4 NO |
Auxiliary contact composition | 2 NO + 2 NC | motor power HP (UL / CSA) | 30 hp at 200 V AC<br />40 hp at 230 V AC<br />75 hp at 460 V AC<br />100 hp at 575 V AC |
Control circuit voltage limits | Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) | Mechanical durability | 10 Mcycles |
Inrush power in VA | 660 VA, 60 Hz 0.3 68 °F (20 °C)) | Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
Operating time | 23...35 ms closing<br />5...15 ms opening | Connections - terminals | Power circuit 2 bars 20 x 3 mm<br />Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)<br />Power circuit connector 1 0.1 in² (95 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection |
Tightening torque | Power circuit 88.5 lbf.in (10 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m) | Mounting Support | Plate |
Heat dissipation | 12…16 W | Standards | IEC 60947-4-1<br />EN 60947-1<br />JIS C8201-4-1<br />EN 60947-4-1<br />IEC 60947-1 |
Product Certifications | RMRoS<br />UL<br />CCC<br />CB<br />RINA<br />DNV<br />LROS (Lloyds register of shipping)<br />ABS<br />BV | Hold-in power consumption in VA | 55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) |
IP degree of protection | IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106 | Protective treatment | TH |
Ambient Air Temperature for Operation | -40…140 °F (-40…60 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
Permissible ambient air temperature around the device | 140…158 °F (60…70 °C) at Uc | Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed6 Gn, 5...300 Hz<br />Shocks contactor open9 Gn for 11 ms<br />Shocks contactor closed15 Gn for 11 ms |
Height | 10.4 in (265 mm) | Width | 7.9 in (200.5 mm) |
Depth | 6.7 in (171 mm) | Operating altitude | 9842.52 ft (3000 m) without derating |
Specifications may be subject to change without notice