schneider LC1F115G622L

Selling Points

  • 1High Performance: Designed for reliable operation in AC-3 applications up to 440V and 115A.
  • 2Easy Installation: Drawer-mounted coil simplifies installation and maintenance.
  • 3Versatile Accessories: Compatible with a wide range of add-on blocks and accessories for customized setups.
  • 4Durable Construction: Built to withstand vibrations and shocks, ensuring long-term reliability.
  • 5Compliance Standards: Meets international standards including IEC 60947-1 and IEC 60947-4-1 for safety and performance.
Product Details
LC1F115G622L
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-1<br />AC-4<br />AC-3
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Uc] control circuit voltage
120 V AC 60 Hz
[Ie] rated operational current
200 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />115 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
200 A (at 104 °F (40 °C))
Rated breaking capacity
920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1100 A 104 °F (40 °C) - 10 s<br />640 A 104 °F (40 °C) - 30 s<br />520 A 104 °F (40 °C) - 1 min<br />400 A 104 °F (40 °C) - 3 min<br />320 A 104 °F (40 °C) - 10 min
Associated fuse rating
125 A aM at <= 440 V<br />200 A gG at <= 440 V
Average impedance
0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
15 W AC-1<br />5 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
55 kW at 380...400 V AC 50/60 Hz (AC-3)<br />59 kW at 415 V AC 50/60 Hz (AC-3)<br />59 kW at 440 V AC 50/60 Hz (AC-3)<br />75 kW at 500 V AC 50/60 Hz (AC-3)<br />80 kW at 660...690 V AC 50/60 Hz (AC-3)<br />65 kW at 1000 V AC 50/60 Hz (AC-3)<br />30 kW at 220...230 V AC 50/60 Hz (AC-3)<br />18.5 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
30 hp at 200 V AC<br />40 hp at 230 V AC<br />75 hp at 460 V AC<br />100 hp at 575 V AC
Control circuit voltage limits
Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
660 VA, 60 Hz 0.3 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
23...35 ms closing<br />5...15 ms opening
Connections - terminals
Power circuit 2 bars 20 x 3 mm<br />Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)<br />Power circuit connector 1 0.1 in² (95 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection
Tightening torque
Power circuit 88.5 lbf.in (10 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)
Mounting Support
Plate
Heat dissipation
12…16 W
Standards
IEC 60947-1<br />JIS C8201-4-1<br />EN 60947-1<br />EN 60947-4-1<br />IEC 60947-4-1
Product Certifications
BV<br />RINA<br />CB<br />DNV<br />ABS<br />LROS (Lloyds register of shipping)<br />UL<br />CCC<br />RMRoS
Hold-in power consumption in VA
55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
-40…140 °F (-40…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
140…158 °F (60…70 °C) at Uc
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed6 Gn, 5...300 Hz<br />Shocks contactor open9 Gn for 11 ms<br />Shocks contactor closed15 Gn for 11 ms
Height
10.4 in (265 mm)
Width
6.4 in (163.3 mm)
Depth
6.7 in (171 mm)
Operating altitude
9842.52 ft (3000 m) without derating

Specifications may be subject to change without notice