schneider LC1F115L622L

Selling Points

  • 1Proven performance for resistive loads and large motor starting applications.
  • 2Available in various voltage options (24v, 120v, 220v) for flexibility.
  • 3Handles up to 115 Amps, suitable for heavy-duty industrial use.
  • 4Ensures durability and reliability in harsh environments.
  • 5Includes a wide range of accessories for easy integration and customization.
Product Details
LC1F115L622L
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-4<br />AC-3<br />AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Uc] control circuit voltage
200...208 V AC 60 Hz
[Ie] rated operational current
200 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />115 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
200 A (at 104 °F (40 °C))
Rated breaking capacity
920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1100 A 104 °F (40 °C) - 10 s<br />640 A 104 °F (40 °C) - 30 s<br />520 A 104 °F (40 °C) - 1 min<br />400 A 104 °F (40 °C) - 3 min<br />320 A 104 °F (40 °C) - 10 min
Associated fuse rating
125 A aM at <= 440 V<br />200 A gG at <= 440 V
Average impedance
0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
55 kW at 380...400 V AC 50/60 Hz (AC-3)<br />59 kW at 415 V AC 50/60 Hz (AC-3)<br />59 kW at 440 V AC 50/60 Hz (AC-3)<br />75 kW at 500 V AC 50/60 Hz (AC-3)<br />80 kW at 660...690 V AC 50/60 Hz (AC-3)<br />65 kW at 1000 V AC 50/60 Hz (AC-3)<br />30 kW at 220...230 V AC 50/60 Hz (AC-3)<br />18.5 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
30 hp at 200 V AC<br />40 hp at 230 V AC<br />75 hp at 460 V AC<br />100 hp at 575 V AC
Control circuit voltage limits
Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Connections - terminals
Power circuit 2 bars 20 x 3 mm<br />Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)<br />Power circuit connector 1 0.1 in² (95 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection
Tightening torque
Power circuit 88.5 lbf.in (10 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)
Mounting Support
Plate
Heat dissipation
12…16 W
Standards
IEC 60947-1<br />EN 60947-4-1<br />JIS C8201-4-1<br />EN 60947-1<br />IEC 60947-4-1
Product Certifications
CB<br />UL<br />LROS (Lloyds register of shipping)<br />RINA<br />ABS<br />CCC<br />BV<br />DNV<br />RMRoS
Hold-in power consumption in VA
55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
-40…140 °F (-40…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
140…158 °F (60…70 °C) at Uc
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed6 Gn, 5...300 Hz<br />Shocks contactor open9 Gn for 11 ms<br />Shocks contactor closed15 Gn for 11 ms
Height
10.4 in (265 mm)
Width
6.4 in (163.3 mm)
Depth
6.7 in (171 mm)
Operating altitude
9842.52 ft (3000 m) without derating

Specifications may be subject to change without notice