schneider LC1F115U5

Selling Points

  • 1High Performance Motor Control: Efficiently manages motor power up to 65 kW at 1000V AC.
  • 2Resistive Load Capability: Handles resistive loads with a rated operational current of 115A at 440V AC.
  • 3AC-3 and AC-1 Compliance: Meets AC-3 and AC-1 utilization categories for diverse applications.
  • 4Reliable Insulation: Features a rated insulation voltage of 1000V AC, conforming to IEC 60947-4-1.
  • 5Durable Design: Withstands mechanical stresses, including 10 million cycles and 2400 cycles/hour at 55°C.
Product Details
LC1F115U5
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-4<br />AC-1<br />AC-3
Poles description
3P
[Ue] rated operational voltage
<= 690 V AC 50/60 Hz<br /><= 460 V DC
[Uc] control circuit voltage
240 V AC 50 Hz
[Ie] rated operational current
200 A (at <104 °F (40 °C)) at <= 440 V AC-1<br />115 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
200 A (at 104 °F (40 °C))
Rated breaking capacity
920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1100 A 104 °F (40 °C) - 10 s<br />640 A 104 °F (40 °C) - 30 s<br />520 A 104 °F (40 °C) - 1 min<br />400 A 104 °F (40 °C) - 3 min<br />320 A 104 °F (40 °C) - 10 min
Associated fuse rating
125 A aM at <= 440 V<br />200 A gG at <= 440 V
Average impedance
0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
15 W AC-1<br />5 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
55 kW at 380...400 V AC 50/60 Hz (AC-3)<br />59 kW at 415 V AC 50/60 Hz (AC-3)<br />59 kW at 440 V AC 50/60 Hz (AC-3)<br />75 kW at 500 V AC 50/60 Hz (AC-3)<br />80 kW at 660...690 V AC 50/60 Hz (AC-3)<br />30 kW at 220...230 V AC 50/60 Hz (AC-3)<br />18.5 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits
Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
550 VA, 50 Hz 0.3 68 °F (20 °C))
Hold-in power consumption in VA
45 VA, 50 Hz 0.3 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
23...35 ms closing<br />5...15 ms opening
Connections - terminals
Power circuit bar 2 20 x 3 mm<br />Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)<br />Power circuit connector 1 0.1 in² (95 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection
Tightening torque
Power circuit 88.5 lbf.in (10 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)
Mounting Support
Plate
Heat dissipation
12…16 W
Standards
JIS C8201-4-1<br />EN 60947-1<br />EN 60947-4-1<br />IEC 60947-4-1<br />IEC 60947-1
Product Certifications
BV<br />UL<br />LROS (Lloyds register of shipping)<br />DNV<br />CB<br />RMRoS<br />RINA<br />ABS<br />CCC
compatibility code
LC1F
Control circuit type
AC 50 Hz
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
-40…140 °F (-40…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
140…158 °F (60…70 °C) at Uc
Height
6.4 in (162 mm)
Width
6.4 in (163.3 mm)
Depth
6.7 in (171 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
7.56 lb(US) (3.43 kg)

Specifications may be subject to change without notice