schneider LC1F115X7

Selling Points

  • 1High Power Rating: 115 Amp, suitable for demanding applications.
  • 2Three Pole Configuration: Ideal for motor control and resistive load management.
  • 3600 VAC Coil: Compatible with a wide range of voltage requirements.
  • 4Three Normally Open Contacts (3 NO): Ensures reliable and efficient circuit control.
  • 5Schneider Electric Quality: Trusted brand known for reliability and performance in industrial settings.
Product Details
LC1F115X7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-1<br />AC-4
Poles description
3P
[Ue] rated operational voltage
<= 690 V AC 50/60 Hz
[Uc] control circuit voltage
600 V AC 40...400 Hz
[Ie] rated operational current
200 A (at <104 °F (40 °C)) at <= 440 V AC-1<br />115 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
200 A (at 104 °F (40 °C))
Rated breaking capacity
920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1100 A 104 °F (40 °C) - 10 s<br />640 A 104 °F (40 °C) - 30 s<br />520 A 104 °F (40 °C) - 1 min<br />400 A 104 °F (40 °C) - 3 min<br />320 A 104 °F (40 °C) - 10 min
Associated fuse rating
125 A aM at <= 440 V<br />200 A gG at <= 440 V
Average impedance
0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
15 W AC-1<br />5 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
55 kW at 380...400 V AC 50/60 Hz (AC-3)<br />59 kW at 415 V AC 50/60 Hz (AC-3)<br />59 kW at 440 V AC 50/60 Hz (AC-3)<br />75 kW at 500 V AC 50/60 Hz (AC-3)<br />80 kW at 660...690 V AC 50/60 Hz (AC-3)<br />30 kW at 220...230 V AC 50/60 Hz (AC-3)<br />18.5 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits
Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.2...0.55 Uc 40...400 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
690…855 VA, 40...400 Hz 0.9 68 °F (20 °C))
Hold-in power consumption in VA
6.6…8.1 VA, 40...400 Hz 0.9 68 °F (20 °C))
Maximum operating rate
1200 cyc/h 131 °F (55 °C)
Operating time
35 ms closing at Uc) <br />130 ms opening at Uc)
Connections - terminals
Power circuit bar 2 20 x 3 mm<br />Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)<br />Power circuit connector 1 0.1 in² (95 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection
Tightening torque
Power circuit 88.5 lbf.in (10 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)
Mounting Support
Plate
Heat dissipation
5.9…7.2 W
Contactor coil voltage
600 V AC standard
Standards
IEC 60947-4-1<br />IEC 60947-1<br />EN 60947-4-1<br />EN 60947-1<br />JIS C8201-4-1
Product Certifications
RINA<br />BV<br />RMRoS<br />CB<br />LROS (Lloyds register of shipping)<br />DNV<br />UL<br />CCC<br />ABS
compatibility code
LC1F
Control circuit type
AC 40...400 Hz
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
-40…140 °F (-40…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
140…158 °F (60…70 °C) at Uc
Height
6.4 in (162 mm)
Width
6.4 in (163.3 mm)
Depth
6.7 in (171 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
7.56 lb(US) (3.43 kg)

Specifications may be subject to change without notice