schneider LC1F185

Selling Points

  • 1High-reliability contactor for demanding industrial applications.
  • 2Suitable for resistive loads up to 1000 Amps and inductive loads up to 800 Amps.
  • 3Designed for motor control and overload protection in various industrial settings.
  • 4Compact design with DIN-rail mounting or screw fixing options.
  • 5Compliant with multiple international electrical standards (IEC, UL, CSA, CCC, EAC).
Product Details
LC1F185
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-4<br />AC-1
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
<= 690 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
275 A 104 °F (40 °C)) <= 440 V AC-1<br />185 A 131 °F (55 °C)) <= 440 V AC-3
Motor power kW
100 kW at 415 V AC 50/60 Hz (AC-3)<br />100 kW at 440 V AC 50/60 Hz (AC-3)<br />110 kW at 500 V AC 50/60 Hz (AC-3)<br />90 kW at 380...400 V AC 50/60 Hz (AC-3)<br />55 kW at 220...240 V AC 50/60 Hz (AC-3)<br />110 kW at 660...690 V AC 50/60 Hz (AC-3)<br />33 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage
24...575 V AC 40...400 Hz with LX9 coil<br />24...460 V DC with LX4 coil<br />100...250 V AC 50/60 Hz with LXE coil<br />100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Irms rated making capacity
1850 A conforming to IEC 60947-4-1
Rated breaking capacity
1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1500 A 104 °F (40 °C) - 10 s<br />920 A 104 °F (40 °C) - 30 s<br />740 A 104 °F (40 °C) - 1 min<br />500 A 104 °F (40 °C) - 3 min<br />400 A 104 °F (40 °C) - 10 min
Associated fuse rating
200 A aM at <= 440 V<br />315 A gG at <= 440 V
Average impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
25 W AC-1<br />12 W AC-3
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil<br />Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.15...0.2 Uc DC with LX4 coil<br />Operational: 85...275 V AC 50/60 Hz with LXE coil<br />Drop-out: 0...60 V AC 50/60 Hz with LXE coil<br />Operational: 85...418 V DC with LXE coil<br />Drop-out: 0...45 V DC with LXE coil
Heat dissipation
8…9.8 W<br />2.2…2.5 W
Operating time
35 ms closing with LX9 coil<br />130 ms opening with LX9 coil<br />30...40 ms closing with LX4 coil<br />30...50 ms opening with LX4 coil<br />40...80 ms closing with LXE coil<br />6...54 ms opening with LXE coil
Mounting Support
Plate
Standards
IEC 60947-4-1<br />EN 60947-1<br />JIS C8201-4-1<br />EN 60947-4-1<br />IEC 60947-1
Product Certifications
ABS<br />LROS (Lloyds register of shipping)<br />RINA<br />CSA<br />CB<br />UL<br />BV<br />RMRoS<br />DNV<br />UKCA
Connections - terminals
Power circuit bar 2 25 x 3 mm<br />Power circuit lugs-ring terminals 1 0.2 in² (150 mm²)<br />Power circuit connector 1 0.2 in² (150 mm²)<br />Power circuit bolted connection<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1.0 0.0004…0.004 in² (0.25…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)solid without cable end
Tightening torque
Power circuit 159.3 lbf.in (18 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)<br />Control circuit 5.3 lbf.in (0.6 N.m)
Mechanical durability
10 Mcycles
Inrush power in VA
950…1180 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX9 coil<br />737…902 VA (at 68 °F (20 °C))with LX4 coil<br />280…310 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />270…320 VA (at 68 °F (20 °C))with LXE coil
Hold-in power consumption in VA
8.9…10.9 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX9 coil<br />4.13…5.07 VA (at 68 °F (20 °C))with LX4 coil<br />4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />2.5…4.0 VA (at 68 °F (20 °C))with LXE coil
Compatibility code
LC1F
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open7 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height
6.9 in (174 mm)
Width
6.6 in (168.5 mm)
Depth
7.1 in (181 mm)
Net Weight
12.02 lb(US) (5.45 kg)
color
-

Specifications may be subject to change without notice