schneider LC1F1854ED

Selling Points

  • 1High reliability with long mechanical and electrical life.
  • 2Suitable for resistive loads up to 1000 Amps and inductive motor applications up to 800 full load Amps.
  • 3Proven performance in large motor starting applications like fans, crushers, pumps, compressors, and overhead cranes.
  • 4Available in 3 poles with screw terminals and compatible with various coil voltages (24V, 120V, 220V).
  • 5Comprehensive line of accessories for enhanced motor control and overload protection.
Product Details
LC1F1854ED
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
<= 460 V DC<br /><= 690 V AC 50/60 Hz
[Uc] control circuit voltage
48 V DC
[Ie] rated operational current
275 A (at <104 °F (40 °C)) at <= 440 V AC-1
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Rated breaking capacity
1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1500 A 104 °F (40 °C) - 10 s<br />920 A 104 °F (40 °C) - 30 s<br />740 A 104 °F (40 °C) - 1 min<br />500 A 104 °F (40 °C) - 3 min<br />400 A 104 °F (40 °C) - 10 min
Associated fuse rating
200 A aM at <= 440 V<br />315 A gG at <= 440 V
Average impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
12 W AC-3<br />25 W AC-1
Overvoltage category
III
power pole contact composition
4 NO
Control circuit voltage limits
Operational 0.85...1.1 Uc 131 °F (55 °C))<br />Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in W
800 W 68 °F (20 °C))
Hold-in power consumption in W
5 W 68 °F (20 °C)
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
30...40 ms closing<br />30...50 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 25 x 3 mm<br />Power circuit lugs-ring terminals 1 0.2 in² (150 mm²)<br />Power circuit connector 1 0.2 in² (150 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 159.3 lbf.in (18 N.m)
Mounting Support
Plate
Heat dissipation
5 W
Standards
JIS C8201-4-1<br />EN 60947-1<br />IEC 60947-1<br />EN 60947-4-1<br />IEC 60947-4-1
Product Certifications
CCC<br />ABS<br />RINA<br />DNV<br />LROS (Lloyds register of shipping)<br />RMRoS<br />BV<br />CB<br />UL
Compatibility code
LC1F
Control circuit type
DC standard
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
6.9 in (174 mm)
Width
8.2 in (208.5 mm)
Depth
7.1 in (181 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
12.02 lb(US) (5.45 kg)

Specifications may be subject to change without notice