schneider LC1F185B722L

Selling Points

  • 1High current rating: 275 A at 440 V AC.
  • 2Wide operating temperature range: -5°C to 55°C.
  • 3Robust mechanical design withstanding vibrations up to 2 G.
  • 4Compliance with international standards: IEC 60947-4-1, EN 60947-1, JIS C8201-4-1.
  • 5Environmentally friendly packaging made from recycled materials.
Product Details
LC1F185B722L
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Uc] control circuit voltage
24 V AC 40...400 Hz
[Ie] rated operational current
275 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />185 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Rated breaking capacity
1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1500 A 104 °F (40 °C) - 10 s<br />920 A 104 °F (40 °C) - 30 s<br />740 A 104 °F (40 °C) - 1 min<br />500 A 104 °F (40 °C) - 3 min<br />400 A 104 °F (40 °C) - 10 min
Associated fuse rating
200 A aM at <= 440 V<br />315 A gG at <= 440 V
Average impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
12 W AC-3<br />25 W AC-1
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
90 kW at 380...400 V AC 50/60 Hz<br />100 kW at 415 V AC 50/60 Hz<br />100 kW at 440 V AC 50/60 Hz<br />110 kW at 500 V AC 50/60 Hz<br />110 kW at 660...690 V AC 50/60 Hz<br />100 kW at 1000 V AC 50/60 Hz<br />55 kW at 220...230 V AC 50/60 Hz
motor power HP (UL / CSA)
50 hp at 200 V AC<br />60 hp at 230 V AC<br />125 hp at 460 V AC<br />150 hp at 575 V AC
Control circuit voltage limits
Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.2...0.55 Uc 50/60 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
970 VA, 60 Hz 0.3 68 °F (20 °C))<br />805 VA, 50 Hz 0.3 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
20...35 ms closing<br />7...15 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection<br />Power circuit 2 bars 25 x 3 mm<br />Power circuit lugs-ring terminals 1 0.2 in² (150 mm²)<br />Power circuit connector 1 0.2 in² (150 mm²)
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 159.3 lbf.in (18 N.m)
Mounting Support
Plate
Heat dissipation
18…24 W
Standards
EN 60947-1<br />IEC 60947-4-1<br />EN 60947-4-1<br />IEC 60947-1<br />JIS C8201-4-1
Product Certifications
ABS<br />LROS (Lloyds register of shipping)<br />RINA<br />CCC<br />DNV<br />UL<br />RMRoS<br />CB<br />BV
Hold-in power consumption in VA
55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))<br />66 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Shocks contactor closed15 Gn for 11 ms<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open7 Gn for 11 ms
Height
12.008 in (305 mm)
Width
6.6 in (168.5 mm)
Depth
7.1 in (181 mm)
Operating altitude
9842.52 ft (3000 m) without derating

Specifications may be subject to change without notice