schneider LC1F185E7

Selling Points

  • 1High-Performance Motor Control: Designed for efficient motor control and resistive load applications.
  • 23-Pole Configuration: Suitable for a wide range of power connections and safety operations.
  • 3185A Current Rating: Handles high currents with reliability and precision.
  • 448V AC Coil: Compatible with various control voltages from 40 to 400 Hz.
  • 5IEC and NEMA Compliance: Meets international standards for electrical safety and performance.
Product Details
LC1F185E7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-1<br />AC-4
Poles description
3P
[Ue] rated operational voltage
<= 460 V DC<br /><= 690 V AC 50/60 Hz
[Uc] control circuit voltage
48 V AC 40...400 Hz
[Ie] rated operational current
275 A (at <104 °F (40 °C)) at <= 440 V AC-1<br />185 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Rated breaking capacity
1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1500 A 104 °F (40 °C) - 10 s<br />920 A 104 °F (40 °C) - 30 s<br />740 A 104 °F (40 °C) - 1 min<br />500 A 104 °F (40 °C) - 3 min<br />400 A 104 °F (40 °C) - 10 min
Associated fuse rating
200 A aM at <= 440 V<br />315 A gG at <= 440 V
Average impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
12 W AC-3<br />25 W AC-1
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
90 kW at 380...400 V AC 50/60 Hz (AC-3)<br />100 kW at 415 V AC 50/60 Hz (AC-3)<br />100 kW at 440 V AC 50/60 Hz (AC-3)<br />110 kW at 500 V AC 50/60 Hz (AC-3)<br />110 kW at 660...690 V AC 50/60 Hz (AC-3)<br />55 kW at 220...230 V AC 50/60 Hz (AC-3)<br />33 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits
Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.2...0.55 Uc 40...400 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
1070 VA, 40...400 Hz 0.9 68 °F (20 °C))
Hold-in power consumption in VA
9.9 VA, 40...400 Hz 0.9 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
35 ms closing at Uc) <br />130 ms opening at Uc)
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 25 x 3 mm<br />Power circuit lugs-ring terminals 1 0.2 in² (150 mm²)<br />Power circuit connector 1 0.2 in² (150 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 159.3 lbf.in (18 N.m)
Mounting Support
Plate
Heat dissipation
8…9.8 W
motor power range
30…50 kW 200…240 V 3 phase<br />55…100 kW 200…240 V 3 phase<br />55…100 kW 380…440 V 3 phase<br />55…100 kW 480…500 V 3 phase<br />110…220 kW 480…500 V 3 phase
Motor starter type
Direct on-line contactor
Contactor coil voltage
48 V AC standard
Standards
EN 60947-4-1<br />EN 60947-1<br />IEC 60947-1<br />IEC 60947-4-1<br />JIS C8201-4-1
Product Certifications
LROS (Lloyds register of shipping)<br />CSA<br />ABS<br />DNV<br />CB<br />RMRoS<br />BV<br />RINA<br />UL<br />UKCA
compatibility code
LC1F
Control circuit type
AC 40...400 Hz
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
6.9 in (174 mm)
Width
6.6 in (168.5 mm)
Depth
7.1 in (181 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
10.25 lb(US) (4.65 kg)