schneider LC1F185F7

Selling Points

  • 1High Current Rating: 185 Amps for robust motor control.
  • 2Versatile Voltage: 600VAC for wide application compatibility.
  • 3Efficient Coil: 110VAC coil with low power consumption.
  • 4Durable Design: Built for high operating rates up to 2400 cycles/hour.
  • 5Multi-Standard Certified: Meets UL, CSA, ABS, LROS, CB, DNV, RINA, RMRoS, BV standards.
Product Details
LC1F185F7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-1<br />AC-3
Poles description
3P
[Ue] rated operational voltage
<= 460 V DC<br /><= 690 V AC 50/60 Hz
[Uc] control circuit voltage
110 V AC 40...400 Hz
[Ie] rated operational current
275 A (at <104 °F (40 °C)) at <= 440 V AC-1<br />185 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Rated breaking capacity
1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1500 A 104 °F (40 °C) - 10 s<br />920 A 104 °F (40 °C) - 30 s<br />740 A 104 °F (40 °C) - 1 min<br />500 A 104 °F (40 °C) - 3 min<br />400 A 104 °F (40 °C) - 10 min
Associated fuse rating
200 A aM at <= 440 V<br />315 A gG at <= 440 V
Average impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
12 W AC-3<br />25 W AC-1
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
90 kW at 380...400 V AC 50/60 Hz (AC-3)<br />100 kW at 415 V AC 50/60 Hz (AC-3)<br />100 kW at 440 V AC 50/60 Hz (AC-3)<br />110 kW at 500 V AC 50/60 Hz (AC-3)<br />110 kW at 660...690 V AC 50/60 Hz (AC-3)<br />55 kW at 220...230 V AC 50/60 Hz (AC-3)<br />33 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits
Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.2...0.55 Uc 40...400 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
1070 VA, 40...400 Hz 0.9 68 °F (20 °C))
Hold-in power consumption in VA
9.9 VA, 40...400 Hz 0.9 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
35 ms closing at Uc) <br />130 ms opening at Uc)
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 25 x 3 mm<br />Power circuit lugs-ring terminals 1 0.2 in² (150 mm²)<br />Power circuit connector 1 0.2 in² (150 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 159.3 lbf.in (18 N.m)
Mounting Support
Plate
Heat dissipation
8…9.8 W
motor power range
30…50 kW 200…240 V 3 phase<br />55…100 kW 200…240 V 3 phase<br />55…100 kW 380…440 V 3 phase<br />55…100 kW 480…500 V 3 phase<br />110…220 kW 480…500 V 3 phase
Motor starter type
Direct on-line contactor
Contactor coil voltage
110 V AC standard
Standards
EN 60947-4-1<br />IEC 60947-4-1<br />EN 60947-1<br />IEC 60947-1<br />JIS C8201-4-1
Product Certifications
UL<br />CSA<br />ABS<br />LROS (Lloyds register of shipping)<br />CB<br />DNV<br />RINA<br />RMRoS<br />BV<br />UKCA
compatibility code
LC1F
Control circuit type
AC 40...400 Hz
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
6.9 in (174 mm)
Width
6.6 in (168.5 mm)
Depth
7.1 in (181 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
10.25 lb(US) (4.65 kg)

Specifications may be subject to change without notice