ParameterValueParameterValue
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-3<br />AC-4<br />AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Uc] control circuit voltage
120 V AC 60 Hz
[Ie] rated operational current
315 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />225 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
315 A (at 104 °F (40 °C))
Rated breaking capacity
1800 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1800 A 104 °F (40 °C) - 10 s<br />1000 A 104 °F (40 °C) - 30 s<br />850 A 104 °F (40 °C) - 1 min<br />560 A 104 °F (40 °C) - 3 min<br />440 A 104 °F (40 °C) - 10 min
Associated fuse rating
315 A gG at <= 440 V<br />250 A aM at <= 440 V
Average impedance
0.32 mOhm - Ith 315 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
32 W AC-1<br />16 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
100 kW at 1000 V AC 50/60 Hz (AC-3)<br />110 kW at 380...400 V AC 50/60 Hz (AC-3)<br />110 kW at 415 V AC 50/60 Hz (AC-3)<br />110 kW at 440 V AC 50/60 Hz (AC-3)<br />129 kW at 500 V AC 50/60 Hz (AC-3)<br />129 kW at 660...690 V AC 50/60 Hz (AC-3)<br />63 kW at 220...230 V AC 50/60 Hz (AC-3)<br />40 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
150 hp at 575 V AC<br />60 hp at 200 V AC<br />75 hp at 230 V AC<br />150 hp at 460 V AC
Control circuit voltage limits
Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
970 VA, 60 Hz 0.3 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
20...35 ms closing<br />7...15 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection<br />Power circuit 2 bars 32 x 4 mm<br />Power circuit lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit connector 1 0.3 in² (185 mm²)
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m)
Mounting Support
Plate
Heat dissipation
18…24 W
Standards
IEC 60947-4-1<br />EN 60947-1<br />JIS C8201-4-1<br />IEC 60947-1<br />EN 60947-4-1
Product Certifications
RINA<br />CCC<br />RMRoS<br />BV<br />CB<br />LROS (Lloyds register of shipping)<br />DNV<br />ABS<br />UL
Hold-in power consumption in VA
66 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Shocks contactor closed15 Gn for 11 ms<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open7 Gn for 11 ms
Height
14.3 in (364 mm)
Width
6.6 in (168.5 mm)
Depth
7.1 in (181 mm)
Operating altitude
9842.52 ft (3000 m) without derating