Product Model
LC1F225X7

Selling Points
- 1High Power Handling: Handles up to 225A at 440V AC-3.
- 2Versatile Applications: Suitable for motor control and resistive load applications.
- 3High Durability: Operates at 2400 cycles/hour withstanding temperatures up to 55°C.
- 4Environmental Sustainability: Compliant with RoHS and Schneider Electric's "Use Better, Use Longer, Use Again" campaign.
- 5Reliable Performance: Meets IEC 60947-4-1 standards with a rated insulation voltage of 1500V.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range | TeSys | Range of Product | TeSys F |
Product or Component Type | Contactor | Device short name | LC1F |
Contactor application | Motor control<br />Resistive load | Utilisation category | AC-1<br />AC-4<br />AC-3 |
Poles description | 3P | [Ue] rated operational voltage | <= 460 V DC<br /><= 690 V AC 50/60 Hz |
[Uc] control circuit voltage | 600 V AC 40...400 Hz | [Ie] rated operational current | 315 A (at <104 °F (40 °C)) at <= 440 V AC-1<br />225 A (at <131 °F (55 °C)) at <= 440 V AC-3 |
[Uimp] rated impulse withstand voltage | 8 kV | [Ith] conventional free air thermal current | 315 A (at 104 °F (40 °C)) |
Rated breaking capacity | 1800 A conforming to IEC 60947-4-1 | [Icw] rated short-time withstand current | 1800 A 104 °F (40 °C) - 10 s<br />1000 A 104 °F (40 °C) - 30 s<br />850 A 104 °F (40 °C) - 1 min<br />560 A 104 °F (40 °C) - 3 min<br />440 A 104 °F (40 °C) - 10 min |
Associated fuse rating | 315 A gG at <= 440 V<br />250 A aM at <= 440 V | Average impedance | 0.32 mOhm - Ith 315 A 50 Hz |
[Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C | Power dissipation per pole | 32 W AC-1<br />16 W AC-3 |
Overvoltage category | III | power pole contact composition | 3 NO |
Motor power kW | 110 kW at 380...400 V AC 50/60 Hz (AC-3)<br />110 kW at 415 V AC 50/60 Hz (AC-3)<br />110 kW at 440 V AC 50/60 Hz (AC-3)<br />129 kW at 500 V AC 50/60 Hz (AC-3)<br />129 kW at 660...690 V AC 50/60 Hz (AC-3)<br />63 kW at 220...230 V AC 50/60 Hz (AC-3)<br />40 kW at 400 V AC 50/60 Hz (AC-4) | Control circuit voltage limits | Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.2...0.55 Uc 40...400 Hz 131 °F (55 °C)) |
Mechanical durability | 10 Mcycles | Inrush power in VA | 950…1180 VA, 40...400 Hz 0.9 68 °F (20 °C)) |
Hold-in power consumption in VA | 8.9…10.9 VA, 40...400 Hz 0.9 68 °F (20 °C)) | Maximum operating rate | 1200 cyc/h 131 °F (55 °C) |
Operating time | 35 ms closing at Uc) <br />130 ms opening at Uc) | Connections - terminals | Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 32 x 4 mm<br />Power circuit lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit connector 1 0.3 in² (185 mm²)<br />Power circuit bolted connection |
Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m) | Mounting Support | Plate |
Heat dissipation | 8…9.8 W | motor power range | 55…100 kW 200…240 V 3 phase<br />110…220 kW 480…500 V 3 phase<br />110…220 kW 380…440 V 3 phase |
Motor starter type | Direct on-line contactor | Contactor coil voltage | 600 V AC standard |
Standards | IEC 60947-1<br />JIS C8201-4-1<br />EN 60947-1<br />IEC 60947-4-1<br />EN 60947-4-1 | Product Certifications | RINA<br />BV<br />CSA<br />UL<br />LROS (Lloyds register of shipping)<br />DNV<br />RMRoS<br />ABS<br />CB |
compatibility code | LC1F | Control circuit type | AC 40...400 Hz |
IP degree of protection | IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106 | Protective treatment | TH |
Ambient Air Temperature for Operation | 23…131 °F (-5…55 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) | Height | 7.8 in (197 mm) |
Width | 6.6 in (168.5 mm) | Depth | 7.1 in (181 mm) |
Operating altitude | 9842.52 ft (3000 m) without derating | Net Weight | 10.47 lb(US) (4.75 kg) |
Specifications may be subject to change without notice