schneider LC1F2654FD

Selling Points

  • 1High Operating Rate: Built for up to 2400 cycles/hour, ensuring reliable performance.
  • 2Durable Design: Withstands environments up to 55°C, providing unmatched reliability and durability.
  • 3Easy Installation: Drawer design allows for easy insertion of the selected coil, simplifying installation.
  • 4Versatile Compatibility: Certified to meet multiple standards (350A/1000V AC-1 Green power), suitable for various industrial settings.
  • 5Premium Quality: High-performance maintenance with secure terminal connections using bars or cables with lugs.
Product Details
LC1F2654FD
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
<= 1000 V AC-1<br /><= 690 V AC-3<br /><= 690 V AC-4<br /><= 460 V DC
[Uc] control circuit voltage
110 V DC
[Ie] rated operational current
350 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
350 A (at 104 °F (40 °C))
Rated breaking capacity
2120 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
2200 A 104 °F (40 °C) - 10 s<br />1230 A 104 °F (40 °C) - 30 s<br />950 A 104 °F (40 °C) - 1 min<br />620 A 104 °F (40 °C) - 3 min<br />480 A 104 °F (40 °C) - 10 min
Associated fuse rating
315 A aM at <= 440 V<br />400 A gG at <= 440 V
Average impedance
0.3 mOhm - Ith 350 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
37 W AC-1
Overvoltage category
III
power pole contact composition
4 NO
Control circuit voltage limits
Operational 0.85...1.1 Uc 131 °F (55 °C))<br />Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in W
750 W 68 °F (20 °C))
Hold-in power consumption in W
5 W 68 °F (20 °C)
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
40...50 ms closing<br />40...65 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 32 x 4 mm<br />Power circuit lugs-ring terminals 1 0.4 in² (240 mm²)<br />Power circuit connector 1 0.4 in² (240 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m)
Mounting Support
Plate
Heat dissipation
5 W
Standards
IEC 60947-4-1<br />IEC 60947-1<br />EN 60947-1<br />JIS C8201-4-1<br />EN 60947-4-1
Product Certifications
RINA<br />BV<br />LROS (Lloyds register of shipping)<br />CB<br />CCC<br />UL<br />ABS<br />DNV<br />RMRoS<br />UKCA
compatibility code
LC1F
Control circuit type
DC standard
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
8.0 in (203 mm)
Width
9.6 in (244.5 mm)
Depth
8.4 in (213 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
18.83 lb(US) (8.54 kg)

Specifications may be subject to change without notice