schneider LC1F330

Selling Points

  • 1High current rating of 330 A for efficient motor control.
  • 2Compatible with a wide range of control circuits including AC and DC.
  • 3Robust design with a long mechanical and electrical life.
  • 4Easy maintenance with drawer-mounted coils and flexible design.
  • 5Suitable for various applications including industrial control systems and HVAC+R.
Product Details
LC1F330
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-4<br />AC-3<br />AC-1
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
400 A 104 °F (40 °C)) <= 440 V AC AC-1<br />330 A 131 °F (55 °C)) <= 440 V AC AC-3
Motor power kW
160 kW at 1000 V AC 50/60 Hz (AC-3)<br />160 kW at 380...400 V AC 50/60 Hz (AC-3)<br />180 kW at 415 V AC 50/60 Hz (AC-3)<br />200 kW at 440 V AC 50/60 Hz (AC-3)<br />200 kW at 500 V AC 50/60 Hz (AC-3)<br />100 kW at 220...240 V AC 50/60 Hz (AC-3)<br />220 kW at 660...690 V AC 50/60 Hz (AC-3)<br />59 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage
24...1000 V AC 40...400 Hz with LX1/LX9 coil<br />24...460 V DC with LX4 coil<br />100...250 V AC 50/60 Hz with LXE coil<br />100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
400 A (at 104 °F (40 °C))
Irms rated making capacity
3300 A AC conforming to IEC 60947-4-1
Rated breaking capacity
2640 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
2650 A 104 °F (40 °C) - 10 s<br />1800 A 104 °F (40 °C) - 30 s<br />1300 A 104 °F (40 °C) - 1 min<br />900 A 104 °F (40 °C) - 3 min<br />750 A 104 °F (40 °C) - 10 min
Associated fuse rating
400 A aM at <= 440 V<br />500 A gG at <= 440 V
Average impedance
0.28 mOhm - Ith 400 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
44 W AC-1<br />31 W AC-3
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil<br />Drop-out: 0.35...0.55 Uc AC 40...400 Hz with LX1/LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.15...0.2 Uc DC with LX4 coil<br />Operational: 85...275 V AC 50/60 Hz with LXE coil<br />Drop-out: 0...60 V AC 50/60 Hz with LXE coil<br />Operational: 85...418 V DC with LXE coil<br />Drop-out: 0...45 V DC with LXE coil
Heat dissipation
8 W<br />2.2…5.5 W
Operating time
40...65 ms closing with LX1/LX9 coil<br />100...170 ms opening with LX1/LX9 coil<br />40...50 ms closing with LX4 coil<br />40...65 ms opening with LX4 coil<br />40...80 ms closing with LXE coil<br />6...54 ms opening with LXE coil
Mounting Support
Plate
Standards
IEC 60947-4-1<br />JIS C8201-4-1<br />EN 60947-1<br />IEC 60947-1<br />EN 60947-4-1
Product Certifications
ABS<br />CSA<br />UL<br />RMRoS<br />DNV<br />CB<br />BV<br />LROS (Lloyds register of shipping)<br />RINA<br />UKCA
Connections - terminals
Power circuit lugs-ring terminals 1 0.4 in² (240 mm²)<br />Power circuit bar 2 30 x 5 mm<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1.0 0.0004…0.004 in² (0.25…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)solid without cable end
Tightening torque
Power circuit 309.8 lbf.in (35 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)<br />Control circuit 5.3 lbf.in (0.6 N.m)
Mechanical durability
10 Mcycles
Inrush power in VA
600…700 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />655…803 VA (at 68 °F (20 °C))with LX4 coil<br />300…350 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />300…310 VA (at 68 °F (20 °C))with LXE coil
Hold-in power consumption in VA
8…10 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />3.68…4.53 VA (at 68 °F (20 °C))with LX4 coil<br />4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />2.5…4.0 VA (at 68 °F (20 °C))with LXE coil
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Operating altitude
9842.52 ft (3000 m) without derating
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open6 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height
8.1 in (206 mm)
Width
8.4 in (213 mm)
Depth
8.6 in (219 mm)
Net Weight
20.9 lb(US) (9.5 kg)

Specifications may be subject to change without notice