schneider LC1F330G722L

Selling Points

  • 1High Performance Motor Control: Designed for motor applications up to 160 kW.
  • 23 Poles, 330A/600V AC: Reliable and efficient contactor for various motor control needs.
  • 3Low Sealed Consumption Coil: 120V AC coil ensures minimal energy loss.
  • 4Robust Construction: Built to withstand harsh environments with IP20 protection.
  • 5Compliance with EU RoHS: Meets European Union's Restriction of Hazardous Substances (RoHS) standards.
Product Details
LC1F330G722L
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-1<br />AC-4
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Uc] control circuit voltage
120 V AC 40...400 Hz
[Ie] rated operational current
400 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />330 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
400 A (at 104 °F (40 °C))
Rated breaking capacity
2640 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
2650 A 104 °F (40 °C) - 10 s<br />1800 A 104 °F (40 °C) - 30 s<br />1300 A 104 °F (40 °C) - 1 min<br />900 A 104 °F (40 °C) - 3 min<br />750 A 104 °F (40 °C) - 10 min
Associated fuse rating
400 A aM at <= 440 V<br />500 A gG at <= 440 V
Average impedance
0.28 mOhm - Ith 400 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
44 W AC-1<br />31 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
160 kW at 380...400 V AC 50/60 Hz (AC-3)<br />180 kW at 415 V AC 50/60 Hz (AC-3)<br />200 kW at 440 V AC 50/60 Hz (AC-3)<br />200 kW at 500 V AC 50/60 Hz (AC-3)<br />220 kW at 660...690 V AC 50/60 Hz (AC-3)<br />160 kW at 1000 V AC 50/60 Hz (AC-3)<br />100 kW at 220...230 V AC 50/60 Hz (AC-3)<br />59 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
75 hp at 200 V AC<br />100 hp at 230 V AC<br />200 hp at 460 V AC<br />250 hp at 575 V AC
Control circuit voltage limits
Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
650 VA, 40...400 Hz 0.9 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
40...65 ms closing<br />100...170 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection<br />Power circuit lugs-ring terminals 1 0.4 in² (240 mm²)<br />Power circuit 2 bars 2 30 x 5 mm
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m)
Mounting Support
Plate
Heat dissipation
8 W
Standards
EN 60947-4-1<br />IEC 60947-4-1<br />IEC 60947-1<br />EN 60947-1<br />JIS C8201-4-1
Product Certifications
RMRoS<br />UL<br />RINA<br />BV<br />CB<br />DNV<br />ABS<br />LROS (Lloyds register of shipping)<br />CSA
Hold-in power consumption in VA
10 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Shocks contactor closed15 Gn for 11 ms<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open6 Gn for 11 ms
Height
14.8 in (375 mm)
Width
8.4 in (213 mm)
Depth
8.6 in (219 mm)
Operating altitude
9842.52 ft (3000 m) without derating

Specifications may be subject to change without notice