schneider LC1F400Q7

Selling Points

  • 1High Power Rating: Handles up to 200 kW at 400 V AC, making it suitable for demanding motor control applications.
  • 2Reliable Performance: Designed with a 10 Mcycle mechanical durability and 2400 cyc/h operating rate at 55°C.
  • 3Compliant with IEC Standards: Meets IEC 60947-4-1 and EN 60947-1 standards for safety and reliability.
  • 4Versatile Connection Options: Features screw clamp terminals and lugs-ring terminals for flexible and solid cable connections.
  • 5Efficient Operation: Low inrush power (1075 VA at 20°C) and hold-in power consumption (15 VA at 20°C), reducing energy costs.
Product Details
LC1F400Q7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-4<br />AC-1<br />AC-3
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /><= 460 V DC
[Uc] control circuit voltage
380 V AC 40...400 Hz
[Ie] rated operational current
500 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />400 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
500 A (at 104 °F (40 °C))
Rated breaking capacity
3200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
3600 A 104 °F (40 °C) - 10 s<br />2400 A 104 °F (40 °C) - 30 s<br />1700 A 104 °F (40 °C) - 1 min<br />1200 A 104 °F (40 °C) - 3 min<br />1000 A 104 °F (40 °C) - 10 min
Associated fuse rating
400 A aM at <= 440 V<br />500 A gG at <= 440 V
Average impedance
0.26 mOhm - Ith 500 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
65 W AC-1<br />42 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
75 kW at 400 V AC 50/60 Hz (AC-4)<br />200 kW at 380...400 V AC 50/60 Hz (AC-3)<br />220 kW at 415 V AC 50/60 Hz (AC-3)<br />250 kW at 440 V AC 50/60 Hz (AC-3)<br />257 kW at 500 V AC 50/60 Hz (AC-3)<br />280 kW at 660...690 V AC 50/60 Hz (AC-3)<br />185 kW at 1000 V AC 50/60 Hz (AC-3)<br />110 kW at 220...230 V AC 50/60 Hz (AC-3)
Control circuit voltage limits
Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
1075 VA, 40...400 Hz 0.9 68 °F (20 °C))
Hold-in power consumption in VA
15 VA, 40...400 Hz 0.9 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
40...65 ms closing<br />100...170 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 30 x 5 mm<br />Power circuit lugs-ring terminals 2 0.2 in² (150 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m)
Mounting Support
Plate
Heat dissipation
14 W
Standards
IEC 60947-4-1<br />EN 60947-1<br />EN 60947-4-1<br />IEC 60947-1<br />JIS C8201-4-1
Product Certifications
LROS (Lloyds register of shipping)<br />CCC<br />RINA<br />ABS<br />BV<br />CB<br />DNV<br />UL<br />RMRoS<br />UKCA
compatibility code
LC1F
Control circuit type
AC 40...400 Hz
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
8.1 in (206 mm)
Width
8.4 in (213 mm)
Depth
8.6 in (219 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
20.06 lb(US) (9.1 kg)

Specifications may be subject to change without notice