schneider LC1F5004ED

Selling Points

  • 1High-reliability design for demanding environments.
  • 24 poles (4NO) configuration for versatile applications.
  • 3700A rating for non-inductive load applications.
  • 4Compatible with 48V DC coil for easy integration.
  • 5Meets EN 60947-4-1 and IEC 60947-4-1 standards.
Product Details
LC1F5004ED
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /><= 460 V DC
[Uc] control circuit voltage
48 V DC
[Ie] rated operational current
700 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
700 A (at 104 °F (40 °C))
Rated breaking capacity
4000 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
4200 A 104 °F (40 °C) - 10 s<br />3200 A 104 °F (40 °C) - 30 s<br />2400 A 104 °F (40 °C) - 1 min<br />1500 A 104 °F (40 °C) - 3 min<br />1200 A 104 °F (40 °C) - 10 min
Associated fuse rating
500 A aM at <= 440 V<br />800 A gG at <= 440 V
Average impedance
0.18 mOhm - Ith 700 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
88 W AC-1
Overvoltage category
III
power pole contact composition
4 NO
Control circuit voltage limits
Operational 0.85...1.1 Uc 131 °F (55 °C))<br />Drop-out 0.2...0.35 Uc 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in W
1100 W 68 °F (20 °C))
Hold-in power consumption in W
6 W 68 °F (20 °C)
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
50...60 ms closing<br />45...60 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 40 x 5 mm<br />Power circuit lugs-ring terminals 2 0.4 in² (240 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m)
Mounting Support
Plate
Heat dissipation
6 W
Standards
JIS C8201-4-1<br />EN 60947-1<br />IEC 60947-1<br />IEC 60947-4-1<br />EN 60947-4-1
Product Certifications
RMRoS<br />DNV<br />ABS<br />CB<br />BV<br />CCC<br />RINA<br />LROS (Lloyds register of shipping)<br />UL
compatibility code
LC1F
Control circuit type
DC standard
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
9.4 in (238 mm)
Width
11.3 in (288 mm)
Depth
9.1 in (232 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
28.55 lb(US) (12.95 kg)

Specifications may be subject to change without notice